MOTOR WITH ENCODER( DIP1 of S4 in ON) + LIMITS SWITCH ON MOTOR PHASES( DIP 2 di S4 in ON).
14)
Always connected the limits switches to
the motor phases, to connect: put Dip 2 of S4 in ON,
encoder/reverse it stops the gate without reverse)
OFF(Dip 2 of S4 in ON),use all security (photocells, safety edges) as is possible.
PROBLEM
Giving a command with the
radiotransmitter or with the key-
switch, the gate does not open.or
not clos
The automation performs only the
manoeuvre of opening or closing
The operator functions by wire but
not with the radiotransmitter.
The electrical limit switch activates
but the motor does not stop.
The gate moves then stops, both in
opening and closing.
When commanded, the motor
starts but the gate does not move.
WARNING: Before sending a radiotransmitter to be repaired, check that the batteries are flat.
50% of all radiotransmitters that return for servicing only have flat batteries.
Page 13 of 14
20,21,22,23,24 of M9.
and made short-circuits on 20,21,22,23,24 of M9. Warning: with test-triac
TROUBLESHOOTING
PROBABLE CAUSE
230 volt mains voltage absent
Emergency STOP present
There is no jumper between the 25 input and
the common.
One of the fuses is burnt out.
Motor power cable not connected or faulty.
The flashing led L2 or L3 points out the
condition of triac TH1 (pilot motor 1) or TH2
(pilot motor 2) in damage.
The photocell, if present, is obstructed or not
The photocell is missing and there is no
jumper between the 18 19 input and the
The safety edge is missing or the bridge is
not present among the entry 15 and 16 and
the commune.
The bridge is missing among the input 37-38
The motors limit switches are missing of is
not present the bridge among the input 20, 21,
23, 24 and the commune.
A key selector NC contact has been used
instead of an NO contact to connect to the 26
The radiotransmitter has not been memorised
or is broken or the battery is flat.
The opening and closing limit switches have
been exchanged.
An NO contact has been used instead of an
The motor force is insufficient and/or the
trigger threshold of the REVERSE is too low.
There is an obstacle in front of the gate; the
hinges are blocked; a motor fixing bracket
has detached.
N.B.: If the problem persists, contact your supplier or the installer.
EQ2009 R 1.6 1.8
Exceptionally it is possible to connect the limit switches on
Dip3 di S4 in OFF(during the last 6 sec. of the stroke, the working of
functioning.
common.
input
NC.
SOLUTIONS
Check master switch
Check for any STOP commands
connected to the 25 input.
If not used, check if there is a jumper on
the 25 input.
Replace the fuse with one of the same
value.
Check the connection of the cable in the
terminal board or replace it.
Remove current to the plant for any
second and subsequently fit the control
panel EQ2009
Check, clean the photocell or remove
the obstacle.
Check the accessory connections and the
presence of the "jumper".
Verify the connections accessories or the
presence of the "bridge."
Verify the presence of the "bridge."
Verify the limit switches of the motor or
the presence of the "bridge."
Check the connections.
Check/change the battery.
Carry out the radiotransmitter
acknowledgement procedure.
Check the connections.
Check if the leaves are in axis, lubricate
if necessary.
Increase the trigger threshold by turning
the P2 P3 trimmer clockwise.
If it is not sufficient, increase the P1
trimmer clockwise and reprogram.
Remove any obstacles from the gate;
restore the hinges, replace or lubricate
them.
Fix the motor fixing bracket.