DANLERS CBU-HBND IP66 빠른 매뉴얼
{카테고리_이름} DANLERS CBU-HBND IP66에 대한 빠른 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. DANLERS CBU-HBND IP66 2 페이지. Ip66 rated ceiling high bay (narrow) passive infra red (pir) occupancy detector & photocell
CBU-HBND IP66
IP66 Rated Ceiling High Bay (Narrow) Passive
Infra Red (PIR) Occupancy Detector & Photocell
Input: 220-240 Vac 50Hz
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
This CBU-HBND IP66 High Bay (Narrow
Detection) Lighting Control has an
IP66 rated weatherproof enclosure
and can be ceiling mounted.
Confi gurable via the free to download
Casambi APP on Google Play or
Apple APP Store.
INSTALLATION
To be installed by a competent person with
reference to BS 7671 or equivalent local standards.
If in doubt consult a qualifi ed electrician.
• Plan where the CBU-HBND IP66 is to be
located (see diagram 1). Switch off supply and
check for hidden cables and pipes.
• Remove the front cover by quarter turning the
four quick release fasteners to the '0' position
(see diagram 4 overleaf).
• Mount the back section of the mounting box in
the required location via the 4 corner holes.
• Thread mains cable carefully through the
required membrane entry point.
• Unclip the internal back plate. Remove the
required knock out if replacing the optional
internal back plate.
• Thread mains cable into the unit. The CBU-
HBND IP66 should be connected as shown in
diagram 2:
L - Live in. N - Neutral in.
• Reclip the internal back plate if required.
• Replace the front cover ensuring the quick
release fasteners are secured in the '1' position.
OPERATION
To check the operation of the CBU-HBND IP66:
• Turn on the supply then after 20 seconds if the
sensor has recognised movement of a person
within its zone of detection the integral red LED
on CBU-HBND IP66 will stay illuminated for 4
seconds before the red LED turns off.
• Thereafter, every time movement is detected by
CBU-HBND IP66 the integral red LED will stay
illuminated for 4 seconds.
The control also features adjustable time out (time
lag) control and daylight threshold control which
are confi gured by the Casambi APP.
PRECAUTIONS
• Do not place the CBU-HBND IP66 near heat
sources, fans or in ventilated ceiling voids.
• CBU-HBND IP66 can be wired in parallel
(sharing the same Live and Neutral).
• Do not place close to, or positioned such
that, any light source points directly into the
CBU-HBND IP66.
• Ensure wires and cables are securely held within
the connection terminals.
• The CBU-HBND IP66 should be protected by a
5 or 6 Ampere mcb or fuse.
• Disconnect the CBU-HBND IP66 from the
circuit before performing insulation testing
of the wiring circuit.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388 E-mail: [email protected]
www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
01/03/18
TECHNICAL DETAILS
INPUT
Voltage:
220 - 240Vac
Frequency:
50Hz
Max. mains current:
0.05A
Standby current:
0.05A
RADIO TRANSCEIVER
Operating frequencies:
2.4... 2,483 GHz
Max. output power:
+4 dBm
LUX PARAMETERS
Range:
5 - 2000 lux
OPERATING CONDITIONS
Note: The temperature difference between the
detection target and the background must be
at least 4 °C.
-20... +40 °C (lout
Ambient temperature:
0.05 A)
Storage temperature:
-25... +75 °C
Max. relative humidity:
0... 80%, non cond.
CONNECTORS
Terminal block
0.5mm
Wire size:
solid or stranded
Wire strip length:
6-7mm
Tightening torque:
0,4 Nm/4 Kgf.cm
MECHANICAL DATA
110mm x 110mm x
Dimensions:
73mm
Weight:
255g (unpacked)
Degree of protection:
IP66
Protection class:
Built-in Class 2
Flame-retardant
Material (casing)
polycarbonate/
Polypropylene.
Finish / Colour
Matt /Grey (RAL 7035)
Protection class:
Built-in Class 2
CONFORMITY AND STANDARDS
EN60669-2-1:2004
EMC emission:
inc. A12:2010
EN60669-2-1:2004
EMC immunity:
inc. A12:2010
EN60669-2-1:2004
Safety:
inc. A12:2010
Complies with WEEE
Environment:
and RoHS directives
5 YEAR WARRANTY
CBU-HBND IP66 comes with a 5 year
warranty from the date of manufacture
and is CE marked.
DETECTION (ND)
Perspective view -
- 2.5mm
2
2
Suggested typical wiring
N
230Vac
L
5A or 6A MCB
or fuse
L - Live in. N - Neutral in.
Two neutral and two live terminals
are available for easy 'loop in' and
'loop out' connection.
plan
110
NARROW
Mounting height
up to 12m
ceiling mounted
Up
to
15m
Up to 3m
DIAGRAM 1
N
N
L
L
DIAGRAM 2
side
73
110
DIAGRAM 3
INS371 CBU-HBND IP66
DETE
Mo
Pers
cei