Installation

Note: Read the safety guidelines under
2.1

Wiring and assembling the signal contact

FAULT
Figure 2: 2-pin terminal block
ELECTRIC SHOCK
Never insert sharp objects (small screwdrivers, wires, etc.) into the connec-
tion terminals for the signal lines, and do not touch the terminals!
Non-adherence to these instructions can lead to death, serious
physical injury or material damage.
For the signal contact to be connected, make sure the following requirements
are met:
The electrical wires are voltage-free.
The connected voltage is limited by a current limitation device or a fuse.
Observe the electrical threshold values for the signal contact.
See "General technical data" on page 16.
 Remove the power connector from the device.
 Connect the signal contact wires with the connectors of the terminal block.
 Mount the terminal block for the signal contact on the front of the device
using the screw locking. Check whether the terminal block is mounted
correctly and screwed on.
Note: Relevant for North America:
The torque for tightening the terminal block for the signal contact on the
device is 3 lb-in (0.34 Nm).
Mounting Instruction MACH104
Release 07 07/2014
"Safety instructions" on page
WARNING
4.
11