1 Calibration Instruction for Salwico ST400 H2S
A
Test points
B
SPAN potentiometer
C
ZERO potentiometer
1.2 Prerequisites
1
Use the arrow keys on the control panel to
manoeuvre through the different menus.
Press the
menu tree.
2
Scroll to 4 Gas Detectors and press
Continue.
3
Scroll to the detector that should be
calibrated and press Options.
4
Scroll to 3 Disable and choose Continue.
5
You have to confirm the disablement before
you can proceed.
Press Disable to continue.
2
right arrow key to access the
5103028_Salwico ST400 H2S_Calibration Instruction_I0_EN_2019_C
Calibration Instruction