1 Calibration Instruction for Salwico ST400 O2
1.5 Reconnecting disabled detectors
All disablements in the Salwico GS5000 gas detection system are presented in the
disablements list. Any enablement is made from this list.
1
Scroll to Menu » Disablements.
2
Choose the detector you just disabled and press Options.
3
Select Reconnect and press Continue.
4
5103029_Salwico ST400 O2_Calibration Instruction_I0_EN_2014_B
Calibration Instruction