Installation Instructions
This method should not be used for outside air damper appli-
cations. The damper will never go to the full close-off position.
This may cause coils to freeze or other system problems. The
AF24-SR (-S) US wired to either the SGA24 or SGF24 can be
used for minimum position setting and still provide full close-off.
Manual Override
The AF series actuators can be manually positioned to ease
installation or for emergency positioning.
Winding the
Locking the
damper actuator
damper actuator
- insert crank handle
- rotate crank handle
- turn handle in direc-
1/2 turn in the direc-
tion of arrow
tion shown by the
"locked" icon.
1. The manual override will only work if no power is available
to the actuator.
2. Insert the manual crank (shipped with the actuator) into
the hexagon hole located on either side of the actuator. An
illustration, located on the label, shows the location.
3. Turn the crank in the direction shown on the label (clock-
wise on the "CW" side, counterclockwise on the "CCW"
side). It will take approximately 19 revolutions to rotate
the full 95° of rotation.
4. To lock the actuator in the required position, rotate the
crank quickly in the opposite direction, 1/2 of a revolution. The
"lock closed" icon on the label shows the correct direction.
5. The manual override may be disengaged in 2 ways.
- Rotate the crank about a 1/4 revolution in the same
direction as the initial winding. The "lock open" icon
shows the correct direction.
- Apply power to wire 1 and 2. The actuator will automati-
cally disengage the override function and will go to the
"on" position in the case of the on-off versions. Or, in the
case of the proportional versions, go to the 0 signal posi-
tion and then go to the position corresponding to the
control signal. The actuator will now work normally.
Testing the installation Without Power
The actuator/damper installation may be tested without power
at the actuator. Refer to the manual positioning section of the
instructions. Move the damper to its full non-fail-safe position
using the manual crank. Disengage the manual position
mechanism and have the damper go to full fail-safe position.
Correct any mechanical problems and retest.
40
Auxiliary Switches
The AF series actuators may be ordered with 2 built-in SPDT
auxiliary switches used for safety interfacing or signalling, for
example, for fan start-up. The switch position near the fail-safe
position is fixed at 5°. The other is adjustable between 25 and
85° of rotation. The crank, supplied with the actuator, or a 3mm
allen wrench is used to adjust the switching position.
Switch Rating
Two methods may be used to adjust the switching point of the
adjustable switch.
Method 1 - See Fig. F
Unlocking the
1
damper actuator
2. Insert the crank into the hexagon shaped hole located in
(2 options)
- rotate crank handle
3. Rotate the crank until the switch pointer is at the desired
1/4 turn in the direction
shown by the
"unlocked" icon.
- remote control by sup-
Method 2 - See Fig. G
plying power to the
1. Position the damper to the point at which you want the
unit for > than 3 sec.
2. Insert the crank into the hexagon shaped hole located in
3. Rotate the switch pointer to just past the switch point indi-
Voltage
Resistive Load
120 VAC
7A
250 VAC
7A
The actuator must be in its fail-safe position.
the center of the adjustable switch pointer.
switch point in degrees as shown.
switch to activate. This may be done by using the manual
override or by providing the appropriate proportional sig-
nal to AF24... modulating type actuator. The position of
the switch pointer is not important during this step.
the center of the adjustable switch pointer.
cating arrow as shown.
AF...series
Rotate with
Factory setting 85°
crank handle
30 40
30 40
50
60
70
80
25...85°
25...85°
Fig. F
Actuator
after locking
Switch operates
30 40
30 40
50
60
70
80
25...85°
25...85°
Fig. G
Inductive Load
5A
2.5A
60° set
30 40
50
50
60
60
70
70
80
80
25...85°
Switch does
not operate
30 40
50
50
60
60
70
70
80
80
25...85°
®