Device Parameter
Device Instance (Default Value = 0)
The router's device instance is a 22-bit value (0–4,194,302). Do
not use 4,194,303 which is reserved by BACnet. Each BACnet
device within the same BACnet internetwork must have a unique
device instance. One must be assigned to the BASRTP-B.
BACnet Ethernet
Ethernet Network (Default Value = 0 — disables BACnet Ethernet)
Most BACnet communication that is carried by Ethernet uses the
BACnet/IP protocol. However, there are still instances in which
the older BACnet Ethernet protocol (ISO 8802-3) is found. The
BASRTP-B allows these two protocols to communicate.
BACnet Ethernet uses Ethernet MAC addresses for station
addressing — unlike BACnet/IP which addresses messages by
means of Internet Protocol (IP) addresses. Each Ethernet MAC
address (often called the physical address) is unique to the
Ethernet network adapter. It is permanently embedded into the
adapter during manufacture and cannot be changed.
It is
composed of six two-digit hexadecimal numbers (00–FF). An
example of an Ethernet MAC address is:
00-08-A1-10-BD-EB
Each Ethernet network adapter has the ability to store an IP
address that is changeable.
This IP address is typically
represented as four decimal values (each is 0–255) separated by
dots. Often called the dotted quad format, an example is:
192.168.92.1
NOTE: Although they may share the same Ethernet physical
network, BACnet Ethernet devices and BACnet/IP devices must
have their own unique network number and these two networks
cannot communicate unless their messages pass through a router.
These network numbers must be in the range of 1–65534 (0 and
65535 are reserved). If the BACnet Ethernet network value is
left at its default value of 0, the BACnet Ethernet function within
the BASRTP-B will be disabled. To prevent message loops, a
subnet must have only one router enabled for BACnet Ethernet.
TD070210-0ID
13