The Binswitch Elite may be mounted horizontally or vertically. 4B offers BAS3 mounting accessory for
this. The end of the sensor must be at least 25mm (one inch) from the bin wall or other metalwork.
It is important that the Binswitch is not located in the direct flow path of any abrasive material. However,
if the Binswitch must be located in the path of an abrasive material, use in conjunction with the BAS3
(Binswitch Abrasion Shield).
Binswitch Elite mounting method is available figure A below:
Fig. A -
Cut and drill holes as shown and attach brasion shield (BAS3) using four M6 bolts. Slide Binswitch into
position and secure with a clip and cover (part of the BAS3 assembly).
1. The supply circuit shall be protected by a suitably rated fuse capable of interrupting a short circuit
current of 1500 Amps.
2. The external connections shall meet the requirements for EPL Ga in accordance with EN 60079-26
and EPL Da in accordance with EN 60079-31.
3. Warning: Potential static ignition risk, clean only with a damp cloth.
4. The integral cable shall be terminated in a suitably certified enclosure or in the safe area.

INSTALLATION

SPECIFIC CONDITIONS OF USE

PAGE 7