All wiring must be In accordance with local and national electrical codes and should be undertaken by
an experienced and qualified electrician.
Always use dust/liquid tight flexible metal conduit with approved fittings to protect the sensor cables.
Use rigid metal conduit to protect the cables from the sensors to the control unit. Conduit systems can
channel water due to ingress and condensation directly to sensors and sensor connections which over
time will adversely affect the performance of the system. As such, the installation of low point conduit
drains is recommended for all sensors.
Supply polarity is not important. However for the BSE2V10C (2 wire), the sensors load MUST have
the same voltage rating as the supply being used and may be connected to either lead. DO NOT
connect to supply without a suitable load.
BSE1V10C - 5 Wire
BSE2V10C - 2 Wire
24 to 240
VAC / VDC
(Universal Supply)

WIRING DIAGRAMS

24 to 240 VAC or
12 to 240 VDC
(Universal Supply)
Blue
Black
Load & Supply Must Have Same Voltage Rating
NOTE
Brown
Blue
Shown In De-Energized State
(200 mA max.)
PAGE 8
Black / Orange
Black
Black / Red
Load