Aplisens SGE-25S.SMART 사용자 설명서 - 페이지 20

{카테고리_이름} Aplisens SGE-25S.SMART에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Aplisens SGE-25S.SMART 20 페이지. Smart level probes
Aplisens SGE-25S.SMART에 대해서도 마찬가지입니다: 사용자 설명서 (20 페이지)

Aplisens SGE-25S.SMART 사용자 설명서
EN.IO.SGE.25.SMART
"Pi" for all types of power supply: see table Z1 below.
Table Z1. Temperature class dependence on ambient temperature Ta and total amount of input power Pi.
4. Connection of probes in Ex version
Figure 1.Ex. Connection for SGE-25.Smart, SGE-25S.Smart, SGE-25C.Smart probes in Ex version.
Connections of the probe and devices in the probe measuring loop must be made in
accordance with intrinsic safety and explosion protection standards and conditions of use
in hazardous areas.
Failure to follow these rules can lead to an explosion and danger to people.
No repairs or other interference with the electrical system of the probe are allowed.
Damage assessment and possible repair can be done only by the manufacturer or a unit
authorized by him.
5. Special conditions for safe use
Probes in the surge arrester version that are labelled as "SA version", do not meet the insulation test
(500 V rms) required by EN 60079-11:2012. This must be taken into account when installing the device.
20
Ta [ºC]
Pi [W]
50
0,75
70
80
40
1,2
65
80
Ta- ambient temperature (measured medium)
Temperature class
T6
T5
T4, group I
T6
T5
T4, group I
EN.IX.SGE.25.SMART
Revision 01.A.001/2021.09