Aplisens SGE-25C 사용자 설명서 - 페이지 12

{카테고리_이름} Aplisens SGE-25C에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Aplisens SGE-25C 16 페이지. Hydrostatic level probes
Aplisens SGE-25C에 대해서도 마찬가지입니다: 사용자 설명서 (20 페이지)

Aplisens SGE-25C 사용자 설명서
EN.IO.SGE
where:
U
- voltage at the terminals of the loop power supply 4...20 mA w [V].
sup
U
- minimum probe voltage
min
- maximum resistance of the supply line [Ω].
R
Lmax

7.2.3. Shielding

The cable shield (green wire) is led out from the probe's power supply and measurement cable.
The manufacturer recommends connecting the probe cable shield to the measuring system
grounding point. The earthing of the cable screen is especially justified in the environment of high
EMC disturbances. In a battery-assisted piezometric stand, the cable screen may or may not be
grounded.

7.3. Overvoltage protection

The probes may be exposed to switching or other overvoltage, for example due to lightning. Surge
diodes are used to protect against overvoltage between the wires of the transmission line. In order
to protect against overvoltage between the transmission line and the earth or the housing (against
which the diodes connected between the lines of the line are not protected), standard and Exi probes.
In the SA version, they are equipped with additional protection in the form of overvoltage limiters.
Additionally, an external protective device can be used, e.g. the UZ-2 system by APLISENS S.A.

7.4. Final Inspection of cabling

After completing the electrical installation of the probe it is necessary to check the following:
is the probe connected according to the information given in section
when using a junction box, that the glands are tightened;
are the diaphragm covers (SGE-25C and SGE-25S) removed.
12
➔ Table 2.
➔ 7.1;
Revision 01.A.001/2021.09