XPERT Card Addressing
Select the desired address for the detector and remove the pips indicated in black. Remove
pips with a small screwdriver.
www.acornfiresecurity.com
4
www.acornfiresecurity.com
Commissioning
It is important that the device be fully tested after installation. Many fault conditions are the
result of simple wiring errors. Check all connections to the unit.
Setup and Test Mode
These modes allow volume adjustment and functional testing locally. In test mode no
volume adjustment is possible.
The required mode is entered via the control panel and is con rmed by a red LED which
ashes once a second on the sounder VAD. Sounder state (on/off) is controlled by placing
a magnet adjacent to the ashing LED. When all LEDs ash, withdraw the magnet. A suit-
able extendable magnetic wand is available, part no. 29650-001.
In setup mode the volume can be adjusted by holding the magnet adjacent to the ash-
ing LED and removing it at the desired volume level. If min or max volume is reached, the
LEDs stop ashing. To alter the direction of adjustment, remove the magnet for one second
and re-apply. Saving the volume setting is performed at the control panel.
Coverage Diagram
Fig 2. Example of coverage pattern
The sides of the included rectangular coverage range from 3.06m X 6.28m to
5.06m X 5.06m
Coverage radius of a single VAD = 2.50m
Centre dark spot radius of a single VAD = 0.97m
Depth of section from the ceiling = 2.40m
Centre to centre spacing of VADs + 1.53m
For alternative mounting heights, please contact Apollo Fire Detectors Limited