Apollo Valves 61YLF Series 설치, 운영, 유지보수 매뉴얼 - 페이지 3
{카테고리_이름} Apollo Valves 61YLF Series에 대한 설치, 운영, 유지보수 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Apollo Valves 61YLF Series 4 페이지. Bronze swing check valve
®
APOLLO
BRONZE SWING CHECK VALVE IOM GUIDE
INSTALLATION
Inspection
Threads of mating pipe must be clean and machined to appropriate ANSI/ASME specifications.
Ends of mating copper tubing or pipe must be square and free of burrs. Use emery cloth to clean and
remove grease and/or oxidation before soldering. Inspect sealing surfaces of valve for cleanliness prior to
installing.
Mounting
Swing check valves can be mounted in either vertical or horizontal position with upward flow or in any
intermediate position. Flow must be by direction of arrow in body.
It is not recommended that swing check valve be mounted in close proximity to reciprocating pumps or
compressors due constant pressure fluctuations which shortens the life of the valve.
NPT connection
It is recommended that the valve is mounted in the closed position. Gently thread valve to mating pipe
by hand until resistance is felt. Using a wrench tighten the valve using the hex flats at the joint being
tightened.
Do not tighten through the valve body using hex flats on opposite end of joint being
tightened.
Solder connection
It is recommended that the valve be in the open position. Care must be taken to apply the proper
amount of solder so that it does not flow into valve seat area. During soldering, the mid-portion of the
valve body should not exceed 300°F. This can be monitored using Tempilstik® or an infra-red
temperature sensor. Depending on the fuel selected and the orientation of the installation it may be
necessary to wrap the valve body with wet rags or employ other heat absorbing techniques. The flame
must be directed away from the valve body, concentrated on the solder cup. The cup should be heated
evenly. Once one of the joints is complete, the valve should be allowed to cool until "cool to the touch"
before beginning the second joint.
Fuel
Propane
Propylene
MAPP Gas
Acetylene
WARNING: Excessive heat input will damage the body seal resulting in leaks at the valve body joint.
Press connection
Valve can be in either closed or open position. Piping must be properly supported so that valve fits
squarely before pressing. Do not solder any joint within 12" of press connection.
Compatible piping: Copper water tube per ASTM B88, Types K, L, & M.
(Not for use with steam service)
Push connection
Valve can be in either closed or open position.
Compatible piping: Copper water tube per ASTM B88, Types K, L, & M, both hard drawn
(Not for use with steam service)
OPERATION
Swing check valve functions by allowing flow forces to move the disc from the closed position to the fully
open position in a sweeping arc motion against a hinge-stop inside the valve body. Due to the weight and
center-of-gravity location of the disc and swing arm assembly, the valve will return to the closed position
should flow become interrupted or reversed.
Swing check valve produces the lowest pressure drop when compared with other check valves of the
same size. They feature a simple design that is easy to maintain. Swing check valves with metal seated
Swing Check 61Y ES 1498 a.pdf.doc
Flame temp w/Oxygen
5122°F (2828°C)
5245°F (2896°C)
5389°F (2976°C)
5720°F (3160°C)
1418 S. Pearl Street Pageland SC USA 29728
3
4
Page 3 of