6. Technical specifications
4E-FMTC
Number of zones
Controls and indications
Microphone (dual)
General paging
Emergency
Power consumption
24V (L-Net)
Audio
Frequency response
Digital audio format
Audio processing
Local network interface
Architecture
Connection
Cabling
Current rating via single link
Max. length of L-Net link
Mechanical
Base dimensions (HxWxL)
Gooseneck mic length
Weight
Housing material
IP rating
Mounting
Operating conditions
Temperature
Relative humidity
Storage temperature
Page 16 of 17
max. 255 zones (global network access)
Mandatory LEDs: power, fault, evac, busy, fireman PTT button;
RGB touchscreen witch user-configurable buttons: zone / group selection,
sources, events, fault/event logging
Condenser, gooseneck
MEMS transducer, handheld, monitored
max. 180mA
100 Hz – 12 kHz
24 kHz sampling, ADPCM compressed
Fixed BP filter, fixed dynamics compression
Master-slave, up to 16 slave devices per C500 main unit
RJ-45, powered daisy chain, digital audio & control data
X-over FTP CAT5e (or higher)
max. 500 mA (up to 8 slave devices) via L-Net port,
250 m
6 x 26 x 21 cm
31.5 cm
1850 g
Steel / ABS
IP 30
Desktop wedge / wall-mounted (incl. wall bracket)
10–40°C
max. 90% (non condensing)
-40–70°C
Author: