I. Modbus TCP/IP - Setup Procedures for dap4 Ethernet Card
Note: When connecting to the Ethernet card, a crossover cable must be used
1. Configure BMS PORT 1 into "BACnet TCP IP" protocol in menu G: Network Config of the
dap4 controller.
2. All Ethernet cards were set up for a DHCP server. You must give the card its factory IP
address to access the card and then switch it to the Ethernet protocol.
3. To do a factory reboot of the card, shut of power to the dap4 controller. Next, press and hold
the button on the card. Now, power on the dap4 controller. Wait approximately 20 seconds
until the status LED begins to blink red 3 times slowly. After the first Red blink, release the
push button. After releasing the button, wait approximately 50 seconds and the card is now
able to be communicated to.
4. The default settings for the card are as follows.
IP address – 172.16.0.1
5. Once you have reset the Ethernet card, you must now configure your network card in your
PC to 172.16.0.*
* any value other then 1.
6. After your PC's network card is configured, open Internet Explorer and enter the card's IP
address (172.16.0.1.)
7. The following prompt will be displayed on your PC's Screen (user name – admin, password –
fadmin)
 
 
Data Aire's dap4 Modbus TCP/IP
Net Mask – 255.255.0.0
Document: 600‐000‐961 version 4.0 
Device Inst - 77000