2651BC Berkel & Rodenrijs
4E-FMWB installation and user guide
Global ring is broken (any place in the ring)
Continuous:
At least one device from the network is missing.
5.1.7. Zone indicators
Zone indicators are strictly related to the corresponding zone button. If a button is not attached to any
zone, then the zone indicators for this button are disabled.
5.1.7.1. Red
Indicates that the zone is in EVAC condition, where the zone is occupied by one of the following audio
signals:
Continuous: LIVE EVAC
Blinking slow: EVAC Message.
5.1.7.2. Yellow
Indicates that the zone is transmitting an ALERT message, and/or is in fault state
Continuous: Zone fault (fault of any line / amplifier included in this zone)
Blinking slow: Zone is transmitting an ALERT Message.
5.1.7.3. Blue
Zone busy / zone selection LED.
Continuous: indicates that the zone is manually selected via
the zone selection button on the local panel
Blinking fast: the zone is occupied by an audio signal, but is
in SILENCE mode (triggered by SILENCE input or manual
SILENCE button)
Blinking slow: indicates that the zone is currently transmitting
an audio signal (except BGM) from another device.
Blinking double: indicates that the zone is currently
transmitting an audio signal from this microphone station.
NOTE: BGM transmission is not indicated.
Page 12 of 17
Author:
Zone A
Manual zone control
DD
OFF
Blink slow
Blink double
Blink fast
continuous
LED indication time chart