Data Aire, Inc. DAP
1 Overview
The DAP III control panel supports a BACnet communication with a BMS for the system
monitoring and control. This document describes all the requirements and configuration
steps to implement the interface with a DAP III panel using the BACnet MS/TP and
Bacnet IP protocol.
2 Hardware Requirements and Installation
2.1 Required Network Card
2.1.1
The BACnet MS/TP protocol interface requires a Data Aire RS-485 Multidrop
communication network card to be installed into the DAP III Display board.
The RS-485 Multidrop card part number is 160-400-383.
Figure 1: Data Aire RS-485 Multidrop Communications Network card
2.1.2
The BACnet IP protocol interface requires a Data Aire Ethernet network card to
be installed into the DAP III Display board. The Ethernet card part number is
160-400-385. This card is compliant with IEEE 802.3/802.3u 100BaseTX
Ethernet standard and auto-negotiation at 10Mbps/ 100 Mbps.
BOARD CONNECTOR
Figure 2: Data Aire Ethernet Communications Network card
Engineering Document - 600-000-460
TM
III BACnet Integration Instructions
TEST JUMPER
Page 3 of 13
BOARD CONNECTOR
END JUMPER
RJ-45 CONNECTOR