7.1.3

Ignition Connection

The ignition input (Brown – pin 12) can be connected to the trailer 24 volt (Light). It will then show if
the trailer is connected to a truck with ignition on (Light turned on). Trailer and datalogger has
separated ground. Remember to mount the 1 kohm resistor R2. On trucks the ground is normally
common and the resistor is not needed.
Can also be connected to the ignition of the refrigeration unit and used to indicate is the cooler is
running.
If this option is not used, the brown wire must be connected to the white wire (Datacold 12 volt).
7.1.4

Configuration of datacold 500, 600 and EuroScanX2

The configuration of the datacold must be done before the Lommy works.
Hold the green button for 2 seconds.
The display shows "Enter PIN"
Factory code is 1111 (press 4 times the blue)
Select menu 11 with the arrow keys
Datacold 500 - Com 1 should be "Thirdparty"
Datacold 600 – Com 1 should be "Partner Protocol"
EuroScan – Com 1 should be "Old ES Protocol"
Com 2 should be Vector, TM or R / T depending on the unit which is mounted.
7.1.5

System configuration

Note the placement and names of the different temperature sensors and set-points. Needed for system
configuration.