DUST FREE
LIGHTSTICK
®
UV INSTALLATION LOCATION
The power module must be mounted directly to
a metal surface.
This will help the ballast dissipate heat. Failing to mount the ballast properly
will void warranty and may lead to pre-mature UV lamp failure.
This device may be installed in an air
handler unit, a cased evaporator coil, or in
an air plenum/duct.
If the UV device is installed on the inlet
side (return air side) of a coil, make sure
that the UV rays are directed away from
any filter medias, plastic duct lining, plastic
components, or accessible doors and
panels.
If the UV device is installed near an air filter,
check with filter manufacturer for UV-C
resistance properties.
If the desired UV installation location is
intended to irradiate an air filter, to neutralize
the microbiological matter on the air filter
surface, such as would be found in the
return air drop of a basement application or
in the return plenum of a horizontal system
in an attic; take precautions as described in
note above, and make sure the UV fixture is
placed on the return side of the filter.
DO NOT INSTALL THE UV FIXTURE ON
EITHER SIDE OF THE FILTER IN HALL /
CLOSET RETURN AIR APPLICATIONS.
WARNING
UV Light Hazard.
Can cause serious eye and skin damage.
Do not look at UV-C light. Wear UV-C eye and
skin protection.
INSTALLATION & OPERATION MANUAL
®
Fig. 3 Cased evaporator coil/furnace
installation.
5