Dataprobe iBoot-Exp 매뉴얼
{카테고리_이름} Dataprobe iBoot-Exp에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Dataprobe iBoot-Exp 5 페이지. Expansion module for iboot
The iBoot-Exp is a remote controlled power On / Off
switch. It is designed to be controlled by
Dataprobe's iBoot-G2+ Web Enabled Power Switch,
as an expansion unit.
iBoot-Exp handles worldwide power from 105-
240VAC. It is capable of switching up to 12 Amps
at 120VAC and 10 Amps at 220 VAC.
Two iBoot-Exp units can be connected and
independently controlled by the iBoot-G2+. For
complete information, refer to the documentation for
the iBoot-G2+.
2.1.
Connect iBoot-G2+
iBoot-G2+ has two Expansion Ports, Exp1 and Exp2 for connection to iBoot-Exp, Connections to the iBoot-Exp are
made using screw terminal blocks.
The screw terminal blocks are on removable connectors for easy cable fabrication. A suitable cable is supplied with
the iBoot-EXP. See Specification below for additional connection information.
iBoot-G2+
iBoot-Exp
V+
+12 Volts Out
V+
I
Control Input
O
G
Ground
G
O
Control Output
I
1. General Description
2. Connections
Function
+12 Volts In
Power. iBoot-G2 to iBoot-Exp
Control Output
Status. iBoot-Exp to iBoot-G2+
Ground
Common Ground
Control Input
Control. iBoot-G2+ to iBoot-Exp
Fig. 2 iBoot Expansion Wiring
Expansion
Module for iBoot
Fig. 1 iBoot Expansion