INSTALLATION AND MAINTENANCE INSTRUCTIONS
WT105
Conventional Heat Detector
SPECIFICATIONS
Height:
Diameter:
Weight:
Installation Temperatures:
Operating Humidity Range:
Operating Voltage Range:
Standby Current:
Maximum Alarm Current (LED on: )
Fixed Temperature Rating:
Rate of Rise Detection:
INSTALLATION
BEFORE INSTALLING
This detector must be installed in compliance with the
control panel installation manual and meet the
requirements of the authority having jurisdiction. In
addition, the National Fire Protection Association has
published
codes,
standards,
practices for the installation and use of detectors,
NFPA 72.
Therefore, the installer must be familiar with these
requirements, with local codes, and any special
requirements of the authority having jurisdiction..
NOTICE: This manual should be left with the
owner/user of this equipment.
IMPORTANT: The detector must be tested and
maintained regularly following NFPA 72 requirements.
The detector should be cleaned at least once a year.
GENERAL DESCRIPTION
Model WT105 is intelligent sensors that utilize a
state-of-the-art thermistor sensing circuit for fast
response. These sensors are designed to provide open
area protection with 50 foot spacing capability. Model
WT105 is a rate-of-rise temperature sensor with 135°F
fixed temperature alarm.
Model WT105 is a rate-of-rise with fixed temperature
alarm thermal detector utilizing a state-of-the-art dual
thermistor sensing circuit. These detectors are
designed to provide open area protection with 50-foot
spacing capability, and are to be used with compatible
control panels only.
Two LEDs on each detector light to provide 360°
visibility of the detector indication.
INSTALLATION
NOTE: All wiring must conform to applicable local
WT105Manual
2.2˝ (55 mm) installed in Base
4.0˝ (103 mm)
5.5 oz. (155 g)
–4°F to 150°F (–20°C to 66°C)
10% to 93% Relative Humidity Non-condensing
9 to 28VDC Volts Non-polarized
40µA @ 24 VDC
≤30mA @ 24 VDC
135°F (57°C)
Responds to greater than 15°F/min
60mmm
and
recommended
Page 1 of
codes, ordinances, and regulations.
NOTE: Verify that all detector bases are installed, that
the initiating-device circuits have been tested, and that the
wiring is correct.
Remove power from initiating-device circuits before
installing detectors.
1. Wire the sensor base per the wiring diagram, Figure 1.
2. Install the sensor into the sensor base. Push the sensor
into the base while turning it clockwise to secure it in
place.
3. After all sensors have been installed, apply power to
the control unit.
4. Test the sensor(s) as described in the TESTING section
of this manual.
5. Notify the proper authorities that the system is in
operation.
Figure 1. Wiring diagram:
2
©
CONVOY
SECURITY