4.4 Setting potentiometer (replacement and setting)
The potentiometer has been calibrated at factory. However, if re-calibration is required, proceed as follows:
Manually rotate the hand wheel of the actuator to fully closed position.
While measuring the resistance between P1 (orange) and P2 (grey), gently rotate the Potentiometer Gear until it reaches between 80 - 120 Ω
(100 Ω preferred).
Engage the Potentiometer Gear into the Point Shaft Gear and use an Hex wrench to tighten the screw.
DANGER:
!
HAZARDOUS VOLTAGE. Make sure all incoming power is disconnected before setting the potentiometer
4.5 Current position transmitter – CPT (optional)
The potentiometer is used for the actuator signal feedback. It reads a resistance value corresponds to the current position of the actuator and transfers
to CPT card. The CPT indicates the current position of the actuator throughout the stroke by a 4 – 20mA output signal.
4.5.1 Standard features
POSITION CONVERSION ACCURACY
AMBIENT TEMPERATURE
DIELECTRIC STRENGTH
INSULATION RESISTANCE
DANGER:
!
HAZARDOUS VOLTAGE. Make sure all incoming power is disconnected before setting the actuator
MODEL
POWER
OUTPUT SIGNAL
OUTPUT IMPEDANCE
RESOLUTION
AMBIENT HUMIDITY
VIBRATION
CPT
110 / 230V AC, 50/60Hz 2VA Max
4~20mA
750Ω Max
Min 1/1000
±0.5 ~ ±1.5%
-20
C To +70
C
0
0
90% RH Max (Non-Condensing)
1500V AC 1 Min
(Input To Output To Power Ground)
ABOVE 500V DC 30MΩ
10G, 0~34Hz
Know-how makes the difference
6