5. COMMISSIONING
WARNING:
CONNECT AU-1P20002G TO THE ELECTRICAL UTILITY GRID ONLY AFTER RECEIVING
PRIOR APPROVAL FROM THE UTILITY COMPANY.
WARNING:
BE AWARE THAT ONLY QUALIFIED PERSONNEL CAN CONNECT
ELECTRICAL UTILITY GRID.
WARNING:
ENSURE THAT ALL AC AND DC WIRING IS CORRECT. ENSURE THAT NONE OF THE AC AND
DC WIRES IS PINCHED OR DAMAGED. ENSURE THAT ALL JUNCTION BOXES ARE PROPERLY CLOSED.
Following these steps to commission the AU-1P20002G PV system:
1. Turn on the AC disconnects or circuit breakers on each AU-1P20002G AC branch
circuit.
2. Turn on the main utility-grid AC circuit breaker. Your system will start producing
power after a few minutes wait time.
3. The AU-1P20002G will start to send performance data over the power lines using
power line communication (PLC) to the AUG-256. The time required for each
AU-1P20002G in the system to communicate to the AUG-256 will vary with the
number of AU-1P20002G in the system.
6. OPERATING INSTRUCTIONS
The AU-1P20002G is powered on when sufficient DC voltage from the module is
applied. The status LED will start flashing after sufficient DC power is applied as an
indication that the AU-1P20002G is live.
Status: standby
The LED light is on by 2 second, and off by 2 seconds
Red: in error.
Orange: no error, but not communicating to AUG-256
Green: no error, and communicating to AUG-256
Status: producing power
The LED light is on by 1 second, and off by 1 second.
Orange: not communicating to AUG-256
Green: communicating to AUG-256
10
AU-1P20002G
TO THE
Status: grounding fault
The LED light is in solid red color.
In case of fault, AUM inverter has multiple protective functions and stops output
power. The fault message may be sent to a connected AUG-256 gateway through
power line communication. For AUM-WiFi, the same alert is sent through WiFi
internet connection, and can be monitored through AustaViewer (please refer to
the tech note "Configuring AUM WiFi"). The alert message is a 16-bit code
Error code
Bit-0
DC over voltage
Bit-1
DC under voltage
Bit-2
hardware error
Bit-3
Inverter over voltage
Bit-4
Frequency over
Bit-5
Frequency under
Bit-6
AC voltage RMS over
Bit-7
AC voltage RMS under
Bit-8
Peak AC voltage over
Bit-9
AC current RMS over
Bit-10
Peak AC current over
Bit-11
Temperature over
Bit-12
ADC error
Bit-13
GFDI fault indicator
Bit-14
Relay fault
Bit-15
PLC Communication Error
7. TROUBLESHOOTING AND MAINTENANCE
WARNING:
DO NOT ATTEMPT TO REPAIR THE AUM-2000; IT CONTAINS NO
USER-SERVICEABLE PARTS. IF TROUBLESHOOTING METHODS FAIL, PLEASE RETURN THE
AUM-2000 TO YOUR DISTRIBUTOR FOR MAINTENANCE.
WARNING:
NEVER DISCONNECT THE DC WIRE CONNECTORS UNDER LOAD. ENSURE THAT
NO CURRENT IS FLOWING IN THE DC WIRES PRIOR TO DISCONNECTING. AN OPAQUE
COVERING MAY BE USED TO COVER THE MODULE PRIOR TO DISCONNECTING
WARNING:
AUM-2000 IS POWERED BY DC POWER FROM PV MODULES. MAKE SURE YOU
DISCONNECT THE DC CONNECTIONS AND RECONNECT DC POWER TO WATCH FOR THE TWO
SECONDS LED ON AND TWO SECONDS LED OFF AFTER DC IS APPLIED.
Error