Brentek PTM-300U 빠른 매뉴얼

{카테고리_이름} Brentek PTM-300U에 대한 빠른 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Brentek PTM-300U 2 페이지.

Brentek PTM-300U 빠른 매뉴얼
rentek
PTM-300U Quick Set-up Guide
This guide is to provide basic instructions on how to quickly get started
and configure the PTM-300U Series Pulse Timing Module.
To configure the PTM-300U:
1. Hold the 2 button for
2. Use the 6 and 5 buttons to change TIMING FUNCTION,
3. Press the 8
4. Use the 6 and 5 buttons to change,
5. Press the 8
6. Use the 6 and 5 buttons to change,
7. Press the 8
TIMING FUNCTION
STRTCH - Defines a (TIMING VALUE
> Typical use: to lengthen or shorten a pulse. [same as INTRVL]
EXTEND - Adds (TIMING VALUE
> Typical use: to extend a pulse. [same as DLYOFF]
MOTION - Retriggerable One-shot function. Time-out (for TIMING VALUE
> Typical uses: Watchdog Timer, Motion Detector, Underspeed detector. [same as WATCHDOG]
DLY ON - Delay-ON (TIMING VALUE
> Typical use: Delay-on-make (power applied)
BUFFER - OUTPUT = INPUT (TIMING VALUE is always 000 mSec)
> Typical uses: Buffer input pulse, (can be used together with I/O FUNCTION to;
Change signal polarity [ H ], Debounce input for 8 mSeconds [ a ])
I/O FUNCTION
A - Normal Operation; Auto-detects input polarity to match same polarity output.
H - Inverts Polarity; Produces compliment NPN or PNP polarity output.
N - Forces output polarity to NPN only.
P - Forces output polarity to PNP only
a - Debounces input for approximately 8 milliseconds. Otherwise same as 'A' (above).
NOTES:
1. IMPORTANT NOTE: Input is ignored and output is inhibited during configuration.
2. If no button is pressed for 5 seconds, configuration is stored and unit will resume normal operation.
3a. Minimum stored TIMING VALUE is 10 milliseconds.
3b. TIMING VALUE is adjustable in 1 mS increments from 10 to 999 mS and 100 mS from 1 to 60 Seconds.
4. On-the-fly timing adjustments may be made in 'real-time' using the 6 and 5 buttons.
IMPORTANT NOTE: Unstored timing changes will be lost if power is lost.
(Unstored TIMING VALUES are denoted with an asterisk '*'.)
5. All LED indicators indicate 'real-time' status.
www.brentek.com
Distributed by: Industrial Products Distributing, Inc.
second. (selection flashes)
button to accept and advance to I/O FUNCTION.
button to accept and advance to TIMING VALUE.
button to accept TIMING VALUE and exit configuration (resumes normal operation).
(refer to PTM-Series Data Sheet for more detailed information)
) output pulse length.
3
) to the OFF-edge.
3
).
3
N G I N
Quick uide
TIMING FUNCTION
TIMING VALUE
) from last ON-edge.
3
800-543-8142
R I N G
I/O FUNCTION
Document No.: PTM-300U-SETUP
Sheet 1 OF 2 Copyright 2007