Note:
For recirculating air defrost ("cd" "FAn"), the fan is switched on during the defrost phase regardless of
the configuration given here.
Digital input 1 & Digital input 2
dLL
c11
c12
Defrost communication with linked defrost start (dLL)
Using electric defrost ("EL"), switching on the configured digital input results in a defrost phase after
!
the expiration of all minimum runtimes (cooling demand, fan, ...). After finishing the defrost, fan and
cooling demand are suppressed until the input signal is cancelled. 90 minutes after finishing the
defrost the controller is starting his regular function even if the input signal is not released. A defrost
is not allowed, if the signal for defrost suppression is switched on, or the last defrost happened less
then 1 hour ago. However, the defrost request is saved and carried out after the removal of the
internal lock.
Using recirculating air- or hot gas defrost ("FAn", "HGE" and "HGS"), the "standard" defrost
!
communication is carried out (see below).
Attention: When using defrost communication with the digital inputs 1 or 2, the goods protection
program should not be configured. Nonobservance results in the alert "EUS".
Cooling request suppression (cSU)
The cooling request is suppressed or interrupted after the minimum running time has elapsed for the
duration of the connection of the digital input or for a maximum of one hour. The fan management is
not affected by this.
Defrost suppression (dSU)
External defrost suppression only takes place after connection of the corresponding configured
digital input. After cancelling the defrost suppression, a defrost can be initiated 1 hour after the
cooling request at the earliest. A defrost that has already been initiated is not interrupted.
Temperature communication (Ecd)
Two MIC QKL mini 2's are also able to communicate with each other using their digital inputs without
a network module. An adaptive setpoint correction of more than two controllers can only be
established using optional network modules, as described under the operating level 2.2.
Directly after a controller requests cooling, a temporarily adjustment of the setpoint temperature of
the remaining controller takes place for the duration of the cooling request. The adapted setpoint
temperature is displayed in the operating level 1 under ''tSA''. The controller percieves the new
setpoint temperature and starts his cooler fan first , followed by his cooling request in the event of a
tendentiously increasing room temperature.
If the remaining controllers of the cooling position detect a tendentially falling room temperature, their
cooling contactor remains inactive whereas the cooler fans remain switched on. After the controller
which initially requested cooling reaches his setpoint temperature, the cooling request and the cooler
fans are switched off under consideration of minimum runtimes. The air cooler fan management as
configured under ''cFA'' is used again. The original setpoint temperature has now priority even for the
former adapted controller.
The procedure described above enables room-temperature driven compressor capacity-control to
be implemented easily.
You can obtain more information on temperature communication with its various possible
applications directly from Cool Expert on request.
Setpoint shift with defrost suppression (SH2)
For the duration of the connection the setpoint value is adjusted by the value configured under "cSS".
During this time, no defrost can be initiated. A defrost that has already been initiated is not interrupted.
The "new" setpoint value is displayed in operating level 1 under "tSA".
Defrost initiation (Edd)
Once all minimum runtimes have expired (cooling request, fan...), a defrosting process is initiated. A
defrost is not permitted if the signal of the defrost suppression is active or the last defrost took place
within less than one hour.
Defrost communication (dLC)
Multiple controllers can work together as a group in one or in several refrigerated units after initiating
a defrost in order to achieve an optimum defrost result. A defrosting controller blocks all other
controllers of a group and thus prevents the occurrence of cost-intensive peak loads. The functions
mentioned below are implemented for the duration of the connection of the configured digital input
regardless of the defrosting procedure selected.
For electric defrosting if the configuration "EL" is selected under "cD". The controller is switched to
!
standby (a maximum of one hour) for the duration of the connection of the correspondingly
configured digital input. After cancelling the signal, a defrost can be initiated 1 hour after the cooling
request at the earliest.
For hot gas defrosting in interconnected and individual refrigeration systems if the configuration
!
"HGE" or "HGS" is selected under "cd". The controller is switched to cooling request to generate hot
gas (for a maximum of one hour) for the duration of the connection of the correspondingly configured
digital input, regardless of the room temperature. After cancelling the signal, a defrost can already
be initiated after 5 minutes of cooling request.
Recirculating air defrosting if the configuration "FAN" is selected under "cD".
!
After the correspondingly configured digital input is connected, a defrosting process is also initiated.
If the signal continues after finishing the defrost, the controller is switched to standby. The controller
switches to normal operation after one hour at most. After cancelling the signal, a defrost can be
reinitiated after two-hours of cooling request at the earliest.
Attention: When using defrost communication with the digital inputs 1 or 2, the goods protection
program should not be configured. Nonobservance results in the alert "EUS".
Factory setting
W E
(All temperature values of the factory setting are indicated in Celsius)
(Config Input 1, Config Input 2)
Defrost communication with linked defrost start
(Defrost lock linked)
Cooling request suppression
cSU
(Cooling suppression)
Defrost suppression
dSU
(Defrost suppression)
Temperature communication
ECd
(External cooling demand)
Setpoint shift with defrost suppression
SH2
(Setpoint shift 2)
Defrost initiation
Edd
(External defrosting demand)
Defrost communication
dLC
(Defrost Lock)
Standby
Stb
(Standby)
Detection of a door opening
dC
(Door contact)
Setpoint shift
SH1
(Setpoint shift 1)
Input not configured
OFF
W E
(OFF)
You can obtain more information on defrost communication with its various possible applications
directly from Cool Expert on request .
Standby (Stb)
The standby mode is initiated immediately for the duration of the connection. The message "Stb"
appears alternately with the room temperature "tL1"in the display. After cancelling the signal, the
controller remains locked for 8 minutes more. This delay time can be adjusted in operating level 2.1,
item "iSd". A safety time can be configured under "cSd". Even in the case of continuous connection
of the digital input, the controller reassumes its control function after the safety time has expired.
Note:
An ongoing defrost is interrupted by the standby and resumed after cancelling the signal.
Detection of a door opening (dC)
The cooling request and fan run are suppressed or interrupted immediately (regardless of all
minimum runtimes). The message "-d-" is displayed alternately with the room temperature for the
duration of door opening.The duration of the door opening in conjunction with "cdd" as well as a
safety temperature under "cdt" can be configured in order to protect the goods against damage.
Setpoint shift (SH1)
The setpoint value is increased or decreased for the duration of the connection by the value
configured under "cSS" and displayed in the operating level 1 under "tSA".
Input not configured (OFF)
No function is performed during connection of the input.
Attention:
The functions of the digital inputs 1 and 2 described here may only be connected using potential-free
contacts.
Setpoint shift
Parameter is only valid in conjunction with "cI1", "SH1" or "cI1", "Sh2" or
"cI2", "SH1" or "cI2", "SH2"
cSS
W E
Correction of the setpoint temperature
If the digital input has been configured accordingly, the setpoint temperature can be increased or
decreased from -30 to +30 K / -54 to +53.5 °R here.
Note:
If circulating air defrosting is used ("cd", "FAn") the resulting setpoint value must not be set to less
than 0 °C / 32 °F! The alert "EUS" follows if this is disregarded.
Duration of door opening
Parameter is only valid in conjunction with "cI1", "dC" or "cI2", "dC"
cdd
W E
Value 1 - 120 minutes
When opening the door, the cooling and fan request are suppressed for the duration of the set time
from 1 to 120 minutes. The set switch-off time can also be activated by an impulse of the door contact.
Time controlled door opening "Off" (OFF)
The cooling and fan request are suppressed for the duration of the door opening.
Safety temperature during door opening
Parameter is only valid in conjunction with "cI1", "dC" or "cI2", "dC"
cdT
W E
Value 0.1 - 10 K / 0.5 - 18 °R
Switch-on temperature after door opening 0.1 - 10 K / 0.5 - 18 °R greater than setpoint.
Safety temperature "Off" (OFF)
The room temperature is ignored for the duration of the door opening.
Alarm time during door opening
Parameter is only valid in conjunction with "cI1", "dC " or "cI2", "dC "
cdA
W E
Value 0 - 120 Minuten
If the door remains open for longer than the configured time, a warning will be given by a periodic
acoustic signal. After further 5 minutes the alert "Edo" is generated.
Standard (Std)
If the door remains open for longer than 120 minutes without interruption, the alert "Edo" is generated
and the controller returns to its control funtion.
External standby safety time
Parameter is only valid in conjunction with "cI1", "Stb" or "cI2", "Stb"
120
cSd
W E
Value 1 - 600 minutes
After the safety time set from 1 to 600 minutes has expired, an external standby is cancelled even if
the signal is still active.
No external safety time configured (OFF)
All control functions remain switched off for the duration of the external standby "Stb" (no time limit).
(Config Setpoint Shift)
Correction of the setpoint temperature
0 . 0
-30 to +30 K / -54 to +53.5 °R
(Config Door Duration)
5
Adjustable value: 1 - 120 minutes
OFF
Time controlled door opening "Off"
(Config Door Temperature)
2
Adjustable value: 0.1 - 10 K / 0,5 - 17.5 °R
OFF
Safety temperature "Off"
(Config Door Alarm)
18
Adjustable value: 0 - 120 minutes
Stdf
Standard
(Config Standy Duration)
Adjustable value: 1 - 600 minutes
OFF
No external safety time configured
6