报警和它的影响
报警的原因
绝缘故障
•
绝缘电阻有下列 2 组响应值
LEDs ALARM 1 ALARM 2 闪烁。
设备故障
•
LED SERVICE 闪烁。
激活绝缘故障定位
•
LED PGH ON 在故障电流通道闪烁。
设备信号报警或设备故障
显示指示的错误以及应用的测量值。
•
在发生 "ALARM 1" 或 "ALARM 2" 的情况下,相关 LED 等闪
•
烁。
如果分配,会间隔发出报警哔哔声。
•
开关分配的报警继电器。
•
开关分配的数字输出。
•
重置报警信息 ( 重置 )
要求 : 不再存在报警的原因。 绝缘电阻必须至少高于响应值
25 % 。
选择 : "RESET" > "RESET" > "OK".
技术数据
出厂设置
( )* =
绝缘协调性 (IEC 60664-1/IEC 60664-3)
额定电压
.......................................................................................................................................... 1000 V
过电压分类
(OVC).................................................................................................................................III
额定脉冲电压
(IEC 60664-1) ....................................................................................................... 8 kV
额定绝缘电压
(IEC 60664-1) .................................................................................................. 1000 V
污染等级
(U
< 690 V) .......................................................................................................................... 3
n
污染等级
(U
< 1000 V) ........................................................................................................................ 2
n
保护隔离介于
和
(≤ 2000 m NN)
.........................................................(L1/+,L2,L3/-)
........................................................................ (A1,A2) – (11,12,14) – (21,22,24) – (E, KE), (X1, ETH, X3, X4)
电压测试、常规测试
(IEC 61010-1) .......................................................................... AC 2.2 kV
电源电压
电源电压范围
U
.................................................................................................. AC/DC 24...240 V
s
U
的公差
............................................................................................................................. -20...+15 %
s
U
的频率范围
........................................................................................................... DC, 50...400 Hz
s
功耗,典型地
50 Hz (400 Hz)........................................................... ≤12 W/21 VA (≤12 W/45 VA)
被监视的 IT 系统
标称系统电压范围
U
.................................................................. AC 0...690 V, DC 0...1000 V
n
U
的公差
..............................................................................................................................AC/DC +15 %
n
U
的频率范围
............................................................................................................. DC, 1...460 Hz
n
响应值
响应值
R
(Alarm 1) ......................................................................................... 1 kΩ...10 MΩ (40 kΩ)*
an1
响应值
R
(Alarm 2) ......................................................................................... 1 kΩ...10 MΩ (10 kΩ)*
an2
操作的不确定性
符合
(
IEC 61557-8)...................
时间相应
响应时间
t
在
R
= 0.5 x R
(R
= 10 kΩ)
an
F
an
an
符合
IEC 61557-8 ..............................................................................
测量回路
测量电压
U
.................................................................................
m
测量电流
I
.................................................................................................................................≤ 403 μA
m
内部电阻
R
, Z
.............................................................................................................................≥ 124 kΩ
i
i
允许外部直流电压
U
.....................................................................................................≤ 1200 V
fg
允许系统泄露电容
C
.............................................
e
接口
现场总线 : 接口 / 协议
....................................................... web server/Modbus TCP/BCOM
iso685_D00022_06_Q_CNEN/10.2016
之间
相关的配置
, ±15 %, min. ±1 kΩ
和
C
= 1 μF
e
相关的配置 , 典型
相关的配置
, ±10 V, ±50 V
取决于相关配置
, 0...1000 μF
Alarm and its effect
Cause of the alarm
Insulation fault
•
The insulation resistance is below both response values
LEDs ALARM 1 and ALARM 2 flash.
Device error
•
LED SERVICE flashes.
Active insulation fault location
•
LED PGH ON blinks according to the locating current.
Device signals alarm or device error
Display indicates error and, where applicable,
•
the measured value.
In the event of "ALARM 1" or "ALARM 2", the associated LEDs
•
flash.
A warning sound beeps at intervals, if assigned.
•
Assigned alarm relays will switch.
•
Assigned digital outputs will switch.
•
Reset alarm messages (Reset)
Requirement: The cause of the alarm is no longer present. The in-
sulation resistance must be at least 25 % higher than the re-
sponse value.
Select: "RESET" > "RESET" > "OK".
Technical data
( )* = factory setting
Insulation co-ordination (IEC 60664-1/IEC 60664-3)
Rated voltage ............................................................................................................................................. 1000 V
Overvoltage category (OVC) ............................................................................................................................... III
Rated impulse voltage (IEC 60664-1) .......................................................................................................... 8 kV
Rated insulation voltage (IEC 60664-1) ................................................................................................... 1000 V
Pollution degree (U
< 690 V) .......................................................................................................................... 3
n
Pollution degree (U
< 1000 V) ........................................................................................................................ 2
n
–
Protective separation (≤ 2000 m NN) between......................................................................(L1/+,L2,L3/-) –
........................................................................ (A1,A2) – (11,12,14) – (21,22,24) – (E, KE), (X1, ETH, X3, X4)
Voltage test, routine test (IEC 61010-1) ............................................................................................. AC 2.2 kV
Supply voltage
Supply voltage range U
....................................................................................................... AC/DC 24...240 V
s
Tolerance of U
............................................................................................................................. -20...+15 %
s
Frequency range of U
............................................................................................................. DC, 50...400 Hz
s
Power consumption typically 50 Hz (400 Hz).................................................. ≤12 W/21 VA (≤12 W/45 VA)
IT system being monitored
Nominal system voltage range U
Tolerance of U
...............................................................................................................................AC/DC +15 %
n
Frequency range of U
............................................................................................................... DC, 1...460 Hz
n
Response values
Response value R
(Alarm 1) .................................................................................... 1 kΩ...10 MΩ (40 kΩ)*
an1
Response value R
(Alarm 2) .................................................................................... 1 kΩ...10 MΩ (10 kΩ)*
an2
Operating uncertainty (acc. to IEC 61557-8) ...................................... profile-dependent, ±15 %, min. ±1 kΩ
Time response
Response time tan at R
= 0.5 x R
F
4 s
acc. to IEC 61557-8 .................................................................................................. profile-dependent, typ. 4 s
Measuring circuit
Measuring voltage U
.................................................................................. profile dependent, ±10 V, ±50 V
m
Measuring current I
.............................................................................................................................≤ 403 μA
m
Internal resistance R
, Z
..........................................................................................................................≥ 124 kΩ
i
i
Permissible extraneous DC voltage U
Permissible system leakage capacitance C
Interfaces
Field bus:Interface/protocol.............................................................................. web server/Modbus TCP/BCOM
ISOMETER® iso685...-CN
..................................................................... AC 0...690 V, DC 0...1000 V
n
= 10 kΩ) and C
(R
= 1 μF
an
an
e
.................................................................................................≤ 1200 V
fg
........................................ dependent on the profile, 0...1000 μF
e