SYSTEM TROUBLESHOOTING (CONTINUED)
UnSaTISfacTorY Performance
SYmPTom
Actuator does not
energize fully
Engine remains below
desired governed speed
normal reaDInG
1. Measure the voltage at the
battery while cranking.
2. Momentarily connect Terminals A and F. The
actuator should move to the full fuel position.
1. Measure the actuator output, Terminals A & B,
while running under governor control.
If unsuccessful in solving instability, contact GAC for assistance.
[email protected] or call: 1-413-233-1888
ProBaBle caUSe of aBnormal reaDInG
1.
If the voltage is less than:
a. 7 V for a 12 V system, or
b. 14 V for a 24 V system,
Then: 1. Check wiring
2. Check circuit protection/relay
3. Check charging system
4. Check battery
1.
Actuator or battery wiring in error
2.
Actuator or linkage binding
3.
Defective actuator
4.
Fuse open. Check for short in actuator or harness.
5.
Check START FUEL and CRANK
1.
If voltage measurement is within 2 V DC of the battery supply
voltage level, then fuel control is restricted from reaching full
fuel position, possibly due to mechanical governor, carburetor
spring, or linkage interference.
2.
Check SPEED, IDLE, GAIN, START FUEL, and CRANK
EEG6550 Enhanced Electronic Governor 5-2020-A1