Adel System CB304A 사용 설명서 - 페이지 2

{카테고리_이름} Adel System CB304A에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Adel System CB304A 4 페이지. 15 cells pb-gel, 25 cells ni-cd intelligent battery charger

Adel System CB304A 사용 설명서
_________________________________________________________Battery Charger
Rail mounting:
The module must be mounted in vertical position.
Other modules must have a minimum vertical distance of 10 cm to this power supply in order to
guarantee sufficient auto convection.
Mounting scheme:
Caution: Switch off the system before connecting the module. Never work on the machine when
it is live.
Functional Characteristics
Charging Level Current: With trimmer from 20% to 100% of In. Select the max. battery charge current
Battery Module (Output 1) 1-2 Pin: Battery input.
Low Battery or Battery replacement: In normal condition with battery in good status:
Diagnosis LED
Normal conditions:
o
Very fast blinking = recovery charging ( when the battery is too low, Under 30 Vdc)
o
Fast blinking = fast charge
o
Slow blinking = trickle charge (floating charge)
Error conditions, Led Fault on and Led Diagnosis:
o
1 blinking = Battery Reverse polarity battery; Bad input voltage battery.
o
2 blinking = Battery not connected.
o
3 blinking = Short circuit battery element
o
5 blinking = Bad battery.(Internal impedance Bad or Bad battery wire connection)
INSTRUCTION MANUAL
Assembly: pull down the plastic block with
a screwdriver, place the CB on the rail and
release the plastic block.
The CB is now assembled on the rail.
estimated from 10 to 30% of the nominal capacity
led fault off and contact close (3-4),
Any fault status of the battery: led fault on and contact open (3-4)
All specification are subject to change without notice
Disassembly: pull down the plastic block and pullout
the module like the arrow in the scheme
2