Adel System CB363A 사용 설명서 - 페이지 3
{카테고리_이름} Adel System CB363A에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Adel System CB363A 4 페이지. Intelligent battery charger
_________________________________________________________Battery Charger
•
Battery Type Configurations
Caution:
Switch off the system before Setting
the jumper.
Posizionamento jumper per la carica:
0.
Open Lead (Charge): Trickle =2.23 Fast=2.40/cell
Battery
Type
1 2 3
1.
Sealed Lead (Charge): Trickle =2.25 Fast=2.40/cell
Battery
Type
1 2 3
•
Cable connection
The following cable cross-sections may be used:
At the Input: 0.2÷2.5 mm
At the Output: 0.2÷2.5 mm
Strip the connection ends: 7mm
Input: The input connection is made by the screw connections L, N, PE
•
Protection
On the primary side: the device is equipped whit a internally fuse T 4 A/250Vac. If the internal fuse is
activated, it is most probable that there is a fault in the device. If happen, the
device must be checked in the factory
On the secondary side Battery and load: The device is electrically protected against short circuits and
Inversion polarity: the module is protected against inversion of battery polarity.
Over current and output short circuit: the unit limits the output power at max. 108W in normal rating.
Battery Test: Automatic. Check polarity and battery. Every 4 hours in trickle charge, make the test of the
battery quality. The fault is signalized with relay commutation and diagnosis led blinking.
Characteristic curve
•
Output current
Internal temperature is electronically controlled. Therefore, battery current is continuous as long as
temperature does not exceed the established limit.
Short circuit and overload
The output current to the battery is selected with the Charge Level trimmer. The maximum power – load
of 108W limits the current to the battery, in 187-264 Vac input range. In 93-132 Vac input range it is
necessary to consider the derating of 60 W max specified in technical features.
Thermal behaviour
The device supplies the nominal output current at ambient temperature of up 40°C. For ambient
temperature of over 40°C, the output current must be reduced by 1% per °C increase in temperature. Max
50°C.
INSTRUCTION MANUAL
2
rigid / flexible
2
rigid / flexible
overload.
All specification are subject to change without notice
2.
Sealed Lead (Charge): Trickle =2.27 Fast=2.40/cell
Battery
Type
1 2 3
3.
Gel Battery (Charge): Trickle =2.30 Fast=2.40/cell
Battery
Type
1 2 3
.
3
CB363A_R2 Eng