5.5 OUTPUT LOAD: TIME BUFFERING MODE (MAINS INPUT OFF)
Some example of buffering time depending on LOAD Output in function to the Ah of the battery.
Buffering Time
BATT1.2 Ah
Load 1.5 A
20 min
Load 3 A
8 min
Load 5 A
3 min
Load 7.5 A
2 min
Load 10 A
No
Load 12 A
No
Load 15 A
No
Load 20 A
No

6 LAY-OUT AND CONNECTIONS

7 INPUT AND OUTPUT LOAD AND BATTERY CONNECTION
7.1.1 Input AC Port L – N:
No.10
1 Phase Switching Power Supplies L, N, PE .
Size 2 and Size 3 BRIDGE ONLY for input 115 Vac, and connect L, N, PE .
7.1.2 Battery Connection Port:
No.1: Connect the battery between: pin. 3 (–) and 4 (+)
One battery (12 Vdc) for CBI12xx;
Two battery (12 Vdc) connected in Series for CBI24xx;
Four battery (12 Vdc) connected in Series for CBI48xx;
7.1.3 Output Load:
No.2:Connect this Output to the load, pin: 1 (–). 2 (+).
BATT 3 Ah
BATT7.2 Ah
60 min
200 min
30 min
120 min
15 min
55 min
10 min
30 min
7 min
20 min
3 min
12 min
No
9 min
No
7 min
BATT12 Ah
BATT100 Ah
400 min
/
240 min
/
100 min
/
60 min
/
45 min
20 h
30 min
600 min
20 min
400 min
13 min
240 min