ADELSYSTEM ALL IN ONE CBI Series 운영자 매뉴얼 - 페이지 7
{카테고리_이름} ADELSYSTEM ALL IN ONE CBI Series에 대한 운영자 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ADELSYSTEM ALL IN ONE CBI Series 12 페이지.
Completely automatic, all devices are suitable to charge most batteries types thank to User Selectable
charging curves. They can charge open lead acid, sealed lead acid, Gel, Ni-Cd and Li-Ion. It is possible to
change or add other charging curves connecting the device to a portable PC.
Caution: Switch off the system before Setting the jumper. Only jumper in position 6 is Refreshed also with
power ON.
Battery Type Selection (Only for CBI485A and CBI485A/S)
Jumper
Jumper Position
Position
(Size 2)
(Size 1)
Open Lead
AGM Low
AGM High
Gel Battery
Battery Type chemistry Selection
Jumper
Position
(Size 1)
Open Lead
(AGM) Low
Gel Battery
NiCd
Li-Ion (4)
Config Mode (5)
Functional Setting
Battery Life test
ON
Boost - Fast
Charge Enable
(3)
"Start from
Battery" (without
Input Mains) (1)
UPS Disabling
(2)
Jumper Position
(Size 3)
Jumper
Jumper Position
Position
(Size 3)
(Size 2)
Dip Switch
Float charge
Position
(Volt/Cell)
(Size 4)
2.23
2.25
2.27
2.30
Dip
Switch
Float charge
Position
(Volt/Cell)
(Size 4)
2.23
2.25
2.30
1.4V/cell
(12V:10 cells)
(24V:20 cells)
(48V:40 cells)
3.45
(12V:4 cells)
(24V:8 cells)
Configure by DPY351 or
ADELVIEWSsystem.
Function
Jumper present or dip
switch ON: Life test enabled
(not for NiCd)
Jumper present: Fast
Charge enabled. It is
possible remote Fast
Charge enabling by
RTCONN cable
Switch ON the system
without the "Mains In Vac",
only the battery is
connected. For connection
to external Push button use
RTCONN cable
If jumper removed: UPS
function disabled
Use RTCONN cable for
connection to external
Contact.
Fast charge
(Volt/Cell)
2.40
2.40
2.40
2.40
Fast charge
(Volt/Cell)
2.40
2.40
2.40
1.5V/cell
(12V:10 cells)
(24V:20 cells)
(48V:40 cells)
3.65
(12V:4 cells)
(24V:8 cells)