Day and Night R4H4 설치 지침 매뉴얼 - 페이지 9

{카테고리_이름} Day and Night R4H4에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Day and Night R4H4 18 페이지. R?410a split system heat pump

INSTALLATION INSTRUCTIONS
Wiring Connections
Make all outdoor electrical supply (Line Voltage)
connections with raintight conduit and fittings. Most
codes require a disconnect switch outdoors within sight of
the unit. Consult local codes for special requirements.
Route electrical supply (Line Voltage) wiring through
knockout hole in bottom of Control Box. Connect wires to
Contactor and Ground Lug according to Wiring Diagram
on unit. Refer to Figure 9.
Route thermostat wiring through rubber grommet in
bottom of Control Box. Low voltage lead wires are
provided in the control box for connection to thermostat
wires (use wire nuts). Refer to Wiring Diagram on unit and
Figure 10 for low voltage wiring examples.
NOTE: Use No. 18 AWG (American Wire Gage)
color−coded, insulated (35 ° C minimum) wire. If
thermostat is located more than 100 feet (30.5 m) from
unit as measured along the control voltage wires, use No.
16 AWG color−coded wires to avoid excessive voltage
drop.
428 01 5302 00
R−410A Split System Heat Pump
Electrical Supply (Line Voltage)
Figure 9
Connections
DISCONNECT
PER NEC AND/OR
LOCAL CODES
L1
FIELD POWER
WIRING
L2
FIELD GROUND
WIRING
CONTACTOR
11
23 or 13
GROUND
LUG
9