Table 2. LED Signals (Continued)
Run LED
Error LED
2 flashes
On
per second
5 flashes
On
per second
5 flashes
Off
per second
7 flashes
7 flashes per
per second
second,
alternating
with Run LED
14 flashes
14 flashes per
per second
second,
alternating
with Run LED
Protection
The UNI/59 module is protected by internal
solid state Polyswitches on the incoming
power and CMnet. These Polyswitches are
not replaceable and will reset themselves if
the condition that caused the fault returns to
normal.
Production Date
To determine when a module was
manufactured, check the module status
report for the module in SuperVision. Refer to
the SuperVision User's Guide for more
information about the module status report.
A sticker on the back of the module also
shows the date the module was
manufactured. The first three characters on
the sticker indicate the type of module. The
next two characters show the year and month
of manufacture. (The month digit is in
hexadecimal.)
Revised 1/3/01 • UNI/59
Condition
Exec halted after frequent
system errors or GFBs
halted
Exec start-up aborted, Boot
is running
Firmware transfer in
progress, Boot is running
Ten second recovery period
after brownout
Brownout
10
© 2001 Automated Logic Corporation