Automated Logic MX800 기술 지침 - 페이지 4

{카테고리_이름} Automated Logic MX800에 대한 기술 지침을 온라인으로 검색하거나 PDF를 다운로드하세요. Automated Logic MX800 5 페이지.

Automated Logic MX800 기술 지침
Be sure the MX800's power is off before
wiring any inputs or outputs. Connect the
output wiring to the screw terminals on the
module as shown in Figure 3.
N / C N / O
B
B
A
A
B
B
A
A
B
B
A
A
B
B
A
A
Figure 3. Digital Output Wiring
NOTE
Do not power pilot relays from the
same transformer that powers the MX800.
To verify each output's operation, lock the
output to a known condition using the
Function Block's Parameter page, then make
sure the equipment actually operates as
specified.
Each digital output can be placed in Manual
or Auto mode by setting the HOA switches
(see Figure 1 on page 2 for the switches'
location). Table 1 shows the status of the
digital output based on the output's
configuration and the HOA switch position.
Table 1. HOA Switch Positions
On
Normally
DO
open
contacts
output
closed
Normally
DO
closed
contacts
output
open
Status page
ON
result (use
channel
numbers
81- 88)
You can monitor the status of the HOA
switches through SuperVision by assigning
Revised 3/29/00 • MX800
D R Y
C O N T A C T
2 4 V A C
Off
Auto
DO
determined
contacts
by FB
open
programming
DO
determined
contacts
by FB
closed
programming
ON
OFF
each switch a digital input in the FB using
channel numbers 81 through 88. Channel 81
corresponds to HOA switch number one;
channel 82 corresponds to HOA switch two,
and so on.
An off status on these channels means the
HOA switch is in Auto mode. An on status
means the HOA switch is in Manual mode.
Channel Numbers
The following tables show the valid channel
numbers for each point on the MX800. Enter
the channel number in Eikon before the
Function Block is made, or on the FB's
Parameter page in SuperVision.
Table 2. Digital Output Channel Numbers
Channel
Point
Signal Type
Number
Digital
11
DO 1
HOA Status†
81
Digital
12
DO 2
HOA Status†
82
Digital
13
DO 3
HOA Status†
83
Digital
14
DO 4
HOA Status†
84
Digital
15
DO 5
HOA Status†
85
Digital
16
DO 6
HOA Status†
86
Digital
17
DO 7
HOA Status†
87
Digital
18
DO 8
HOA Status†
88
† Use digital input microblocks to
monitor the status of HOA Switches.
Troubleshooting
LEDs
The MX800 module has several LED
indicators to show the status of certain
functions.
Power - lights when power is being supplied
to the module.
Run - flashes to indicate a normal condition.
4
© 2000 Automated Logic Corporation