Using the MX400
The MX400 is part of the M-Line, which
allows a complete controls system to be built
a piece at a time. By attaching the MX400
expander to M or Mcpu controllers, your
system can grow as the size of the job
increases. The MX400 has four digital
outputs.
The MX400 provides the communications
circuitry and removable screw terminals for
I/O connections.
CAUTION Changes or modifications to this
unit not expressly approved by the party
responsible for compliance could void the
user's authority to operate equipment.
NOTE This equipment has been tested and
found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide
reasonable protection against harmful
interference when the equipment is operated
in a commercial environment. This
equipment generates, uses, and can radiate
radio frequency energy and, if not installed
and used in accordance with the instruction
manual, may cause harmful interference to
3 3/4"
9.5cm
1/4"
0.6cm
Revised 4/3/00 • MX400
11 5/16"
28.73cm
I/O
Expansion
Expander
Run
Comm
MX400
Open Energy
Management Equipment
CONTROL MODULE
Expander
E143900
Address
TYPE: 00440
I/O
Expansion
, 2 ( [ S D Q V L R Q
5 R W D U \ $ G G U H V V
Figure 1. Module Dimensions and Layout
2
radio communications. Operation of this
equipment in a residential area is likely to
cause harmful interference in which case the
user will be required to correct the
interference at his own expense.
Specifications
Power 24VAC ± 10%, 50-60Hz (24VAC
±10%, 60Hz for UUKL Smoke Control
Systems), 8VA power consumption
single Class 2 source only, 100VA or less.
Digital Outputs four digital outputs, relay
contacts rated at 3A resistive @ 24VAC.
Configurable as normally open or
normally closed.
Environmental Operating Range 0° to
130°F (-17.8° to 54.4°C); 10 to 90%
relative humidity, non-condensing. (For
UUKL Smoke Control Systems, 32 to
120.2 °F [0 to 49 °C]; 10 to 85% relative
humidity, non-condensing.)
Status Indication Visual (LED) status of
expansion communication, running, and
power.
Protection Voltage, current, and ESD
protection on incoming power.
Listed by UL 916 (PAZX), cUL C22.2 No.
205-M1983 (PAZX7), FCC Part 15 -
Subpart B - Class A.
Power
On Off
Class 2
Use Single
24 Vac
Class 2
50-60 Hz
Gnd
Source Only
8 VA 0.33A
Use Copper
24 Vac
Conductors Only
8
D0-4
7
6
D0-3
5
4
D0-2
3
R
2
D0-1
1
88FO
Output
Contacts
N/C N/O