Connections for 277Vac line voltage (Figure 6):
a. Install three red clips (provided) one on the red wire (heater),
and white and orange wires (transformer).
b. Self-connect red wire (heater) on its own clip (electrical cap).
c. Connect white wire (heater) to clip of white wire (transformer).
d. Connect red wire (thermostat) to clip of orange wire
(transformer).
Thermostat
Red
White(Netural)
Black(120V)
Orange(277V)
Figure 6
NEXUS (option): refer to page 4 for electrical connections and
commissioning.
8. Install the batteries (if shipped separately) and connect the battery
wires to the charger board. Each battery has its own cable and
must be connected to the charger.
9. Tighten the batteries and cables with the flexible Velcro strap.
10. For vertical pole mount: in addition to the Velcro strap, install the
metal strap and screws provided in the installation kit (Fig 1.) to
hold the battery(ies).
11. Close the cover and tighten the screws.
SCREWS MUST BE TORQUED TO AT
LEAST 12INLB TO ENSURE A WATER-
WARNING:
TIGHT SEAL BETWEEN THE COVER AND
HOUSING.
12. Turn on AC power.
Manual Testing
The equipment comes standard with a one-
button infrared remote control.
Before starting manual testing remove plastic
tab from battery compartment on remote
control.
To initiate a test: orient the remote control
towards the pilot light of the unit and press the
TEST button.
13. Test function (power on, stand-by): press the TEST button, the unit
will start a one-minute test. Pressing the button again will abort the
test in progress.
14. Load disconnect: this option can be used during a power failure to
save battery power during daylight hours. Press the TEST button,
the emergency lights will turn off. By pressing the test button again
the emergency lights will turn back on.
15. On-charger manual test: the unit also has a test button installed on
the charger module located on the bottom of the unit (See figure 7).
This is useful during maintenance, with the unit door open. The
button performs the same functions as the remote control.
Automatic self-test and diagnostic (Option)
16. Self-test: Once power is supplied to the unit it will automatically
initiate a routine self-test calendar as follows:
a. Verifies battery connection, battery failure, charger board failure
and lamps failure.
Emergi-Lite®
Tel: (888) 552-6467
®
White
Red
Heater Pad
Yellow
Fax: (800) 316-4515
HP Series Battery Unit for hazardous locations
b. Executes one-minute monthly self-test
c. Executes a 30 -minute self-test every 6th month
d. Executes a 90 -minute self-test every 12th month
17. Diagnostic: The unit is equipped with a bi-color LED pilot light and
indicates the following status:
a. Green color: AC-on / self-test
b. Red color: Service alarm
A diagnostic label is placed on the unit cover.
O
Green
O
Green
O
Red
Steady On
O
Red
One Blink
OO
Red
Two Blinks
OOO
Red
Three Blinks
OOOO
Red
Four Blinks
Transfer time delay (Option)
This feature works when the AC power is restored: it keeps the
emergency lights "on" for a period of: 5, 10 or 15 minutes (factory set).
If the battery depletes before the end of the time delay, the lamps turn
off and the unit goes in stand-by mode.
The Time Delay feature can be enabled or disabled in the field with the
following procedure (See figure 7):
a. Make sure that the battery and the AC main power are both
disconnected.
b. Disconnect the jumper JP4 to activate the Time Delay
c. Continue with the standard installation
enabled
No TD
JP4
Buzzer Silent
"ON"
JP7
Test switch
Figure 7 Charger module
Audible service alarm (Option)
This function acts in case of a Service alarm by generating a beep
every two seconds.
During a service alarm the beep can be silenced by pressing the
remote control test switch.
The audible service alarm can also be permanently disabled in the field
by disconnecting the jumper JP7 (See figure 7).
www.emergi-lite.com
Steady
AC On
Blinking
Testing Mode
Battery disconnect or
Lamp disconnect
Battery Failure
Charger Failure
Lamp Failure
Heater Failure
TD
Low‐voltage
transformer
secondary
Load Fuse
Battery
On‐charger test switch
11/17 750.0020 Rev. A