ADEMCO VISTA-15P 프로그래밍 매뉴얼 - 페이지 16
{카테고리_이름} ADEMCO VISTA-15P에 대한 프로그래밍 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ADEMCO VISTA-15P 17 페이지. Programming auto arming and disarming schedules
ADEMCO VISTA-15P에 대해서도 마찬가지입니다: 빠른 설치 매뉴얼 (2 페이지), 프로그래밍 매뉴얼 (17 페이지), 사용자 설명서 (20 페이지), 빠른 설치 매뉴얼 (2 페이지), 빠른 설치 매뉴얼 (2 페이지), 프로그래밍 매뉴얼 (2 페이지), 빠른 매뉴얼 (2 페이지)
- 1. To Enter Programming Mode
- 2. To Exit Programming Mode
- 3. Reporting Options
- 4. Configurable Zone Types Worksheets
- 5. Output Type
- 6. Zone Type Definitions
- 7. ALPHA VOCABULARY LIST (for Entering Zone Descriptors)
- 8. CHARACTER (ASCII) CHART (for Adding Custom Words)
- 9. Series Transmitter Input Loop Identification
- 10. Table of Device Addresses
24-HR BATTERY STANDBY REQUIRED FOR
BATTERY FUSE
FIRE INSTALLATIONS. USE 12V, 17.2AH
FOR REPLACEMENT,
3A
BATTERY FOR 600mA AUX POWER. SEE
USE SAME VALUE
INSTRUCTIONS.
(e.g. ADEMCO No. 90-12)
BATTERY CAPACITY FOR EMERGENCY
BURGLARY STANDBY USE AT LEAST 4 HRS
CHARGING VOLTAGE
BLACK
BATTERY
13.8VDC. MAXIMUM
+
FLYING LEADS
12V, 4AH
CHARGING CURRENT
RED
FOR BATTERY
650mA.
+
CONNECTION
SEALED LEAD-ACID TYPE.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3 YRS.
TO DETERMINE TOTAL STANDBY LOAD
ON BATTERY, ADD 100mA TO TOTAL OF
AUX. POWER OUTPUT AND REMOTE
KEYPAD CURRENTS.
USE UL LISTED LIMITED ENERGY
1
2
CABLE FOR ALL CONNECTIONS
CLASS 2 PLUG-IN TRANSFORMER
16.5VAC, 25VA
(e.g. ADEMCO No. 1321).
(USE No. 1321CN IN CANADA)
USE 4300 / 1321X10 TRANSFORMER
INTERFACE IN PLACE OF 1321 OR
1321CN WHEN POWER LINE CARRIER
DEVICES ARE BEING USED. (SEE
TO 110VAC
INSTRUCTIONS FOR CONNECTIONS)
UNSWITCHED
THIS EQUIPMENT SHOULD BE INSTALLED
OUTLET (24HR)
IN ACCORDANCE WITH THE NATIONAL
FIRE PROTECTION ASSOCIATION'S
+
STANDARD 72, CHAPTER 2 (NATIONAL
FIRE PROTECTION ASSOCIATION,
ALARM OUTPUT
BATTERY-MARCH PARK, QUINCY,MA
10.5–13.8VDC, 2A MAX.
02269).
(600mA MAX. FOR UL
PRINTED INFORMATION
USAGE, INCLUDING
DESCRIBING PROPER INSTALLATION,
AUX POWER) STEADY
OPERATION,TESTING, MAINTENANCE,
EVACUATION PLANNING AND REPAIR
FOR BURGLARY/PANIC,
SERVICE IS TO BE PROVIDED WITH THIS
TEMPORAL PULSE
EQUIPMENT.
SOUNDING FOR FIRE.
CAN USE ADEMCO No. 702
CONNECTION OF THE FIRE ALARM
SIREN, OR 12V BELL).
SIGNAL TO A FIRE ALARM
SEE INSTRUCTIONS.
HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH THE
PERMISSION OF THE LOCAL AUTHORITY
HAVING JURISDICTION. THE BURGLAR
FOR COMPLETE
ALARM SIGNAL SHALL NOT BE
INFORMATION, SEE
CONNECTED TO A POLICE EMERGENCY
INSTRUCTIONS K5305-1
NUMBER.
ASSEMBLED IN MEXICO
8-PIN CONNECTOR
USED FOR 4300/1321X10
TRANSFORMER
CONNECTIONS AND FOR
ON-BOARD TRIGGERS
SEE INSTRUCTIONS.
(USE SA4120XM-1
1 2 3 4
5 6
7 8
CABLE)
SYNC
COM
TO
TRANS.
DATA
TO TERM 4
RED JUMPER
TO TERM 5
CUT FOR BELL SUPERVISION.
TO TERM 6
ALSO, CONNECT 2000 OHM
TO TERM 7
RESISTOR DIRECTLY ACROSS
SOUNDER.
3
4
5
6
7
8
9
+
L
AUX. POWER
OUTPUT
10.5-13.8VDC
600mA MAX.
(500mA MAX.
FOR UL
INSTALLATIONS)
ALL OUTPUTS
ARE POWER
LIMITED.
2000
NOTE:
OHMS
KEYPAD (S)
EOLR
CURRENT (IN
BOTH
REMOTE
PARTITIONS)
KEYPADS
12
AND ALL
AND OTHER
OTHER DEVICES
ADDRESSABLE
DRAWING
DEVICES
POWER FROM
(e.g. 5800TM,
2k
TERMS 4 & 5
4285/4286, LRR,
MUST BE
4219, 4229,
INCLUDED IN
4204, 5881)
AUX CURRENT
2k
DRAIN
REMOTE KEYPADS
CALCULATIONS.
CAN USE 6150 OR 6160
KEYPADS. LOCAL
PROGRAMMING
2k
MUST BE DONE WITH A
ZONE 3
6139/6160, BUT NEED NOT
REMAIN IN THE SYSTEM
TYPICAL WIRING FOR
DOUBLE BALANCED ZONE
(SET TO ADDRESS 16).
(VISTA-20P ONLY)
VISTA-20P/VISTA-15P
SUMMARY OF CONNECTIONS
ADEMCO No. 4219
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
-OR-
ADEMCO No. 4229
WIRED EXPANSION/RELAY MODULE
BLK
(8 ADD'L EOLR WIRED ZONES PLUS 2
OUTPUT RELAYS)
RED
-OR-
GRN
ADEMCO No. 4204 RELAY MODULE
YEL
(4 OUTPUT RELAYS)
AND/OR
ADEMCO 5881* Type
RF RECEIVER
BLK
WIRELESS ZONES
BLK
RED
5881L:
UP TO 8
RED
GRN
5881M: UP TO 16
GRN
5881H: UP TO 64
YEL
*5882 IN CANADA
YEL
10
11
12
13
14
15
16
17
2000
2000
2000
2000
2000
OHMS
OHMS
OHMS
OHMS
OHMS
EOLR
EOLR
EOLR
EOLR
EOLR
•
MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
• RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
13
14
•
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
ZONE
TAMPER
2k
CONTACTS
PAIRS
10
11
2 / 10
3 / 11
4 / 12
ZONE 2
5 / 13
TAMPER
2k
CONTACTS
6 / 14
3k
7 / 15
8 / 16
ZONE 10
2k
6.2k
ZONE 4
TYPICAL WIRING FOR
ALL DEVICES AND ACCESSORIES
ZONE DOUBLING
USED IN A CANADIAN INSTALLATION
(VISTA-20P ONLY)
MUST BE LISTED FOR USE IN CANADA
4-WIRE
RELAY
SMOKE DETECTOR
PROGRAM RELAY
CONNECTIONS
AS ZONE TYPE 54
SET UNIT'S
(FIRE ZONE RESET)
DIP SWITCH
FOR DEVICE
+
5
AUX PWR
ADDRESSES
_
OUTPUT
_
BLK
7 - 15
4
TERMINALS
SEE
INSTRUCTIONS.
+
_
VIOLET
4-WIRE SMOKE
OR COMBUSTION
SET
DETECTOR
RECEIVER'S
2000
DIP SWITCH
OHMS
FOR DEVICE
EOLR
TO ZONES 2-8
ADDRESS
TERM. ( )
+
OF "0".
HEAT
SEE
TO ZONES 2-8
DETECTOR
_
INSTRUCTIONS.
TERM. ( )
18
19
20
21
22
23
24
TIP
RING
TIP
RING
(BROWN)
(GRAY)
(GREEN)
(RED)
INCOMING
HANDSET
PHONE LINE
TELEPHONE WIRING
(VIA RJ31X* JACK AND DIRECT
CONNECT CORD)
*CA38A IN CANADA
DOC LOAD NO.: 3
FOR CONNECTION OF OPTIONAL 4285 OR 4286 VIP
MODULES TO PHONE TERMINALS, SEE INSTRUCTIONS.
2000
2000
OHMS
OHMS
WARNING:
TO PREVENT RISK OF SHOCK,
EOLR
EOLR
DISCONNECT TELEPHONE LINE AT TELCO
JACK BEFORE SERVICING THIS UNIT.
COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. 5GBUSA-44003-AL-E
RINGER EQUIVALENCE: 0.1B.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS
SYSTEM. IN ADDITION, THIS SYSTEM MUST BE CHECKED BY A QUALIFIED
TECHNICIAN AT LEAST ONCE EVERY THREE (3) YEARS.
+
RED
EOL
POWER
SUPERVISION
RELAY
MODULE
A77-716B
25
EARTH
GROUND
SEE
INSTRUCTIONS
FOR PROPER
GROUNDING
V20P_V15P-SOC-V0