DynaGen GSC400 Series 캘리브레이션 유틸리티 매뉴얼 - 페이지 11

{카테고리_이름} DynaGen GSC400 Series에 대한 캘리브레이션 유틸리티 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. DynaGen GSC400 Series 18 페이지. For generator
DynaGen GSC400 Series에 대해서도 마찬가지입니다: 프로그래머 매뉴얼 (4 페이지)

DynaGen GSC400 Series 캘리브레이션 유틸리티 매뉴얼
2. Current Only – Does not modify the AC Voltage calibration constants.

3.3.1 Equipment

If you are doing an AC current calibration you will need the following:
1. An accurate instrument (e.g. ammeter or multimeter set to AC current) to
measure current from the generator. Measure as close to the CTs as
possible.
2. A load source to generate two different currents for the calibration
preferably at 25% and 75% of normal maximum load.
3. Knowledge of the number of phases the GSC400 is measuring (A, B, C).
To determine this look at the AC Voltage connections on the back of the
GSC400.
If you are doing an AC voltage calibration you will need the following:
1. A voltmeter to measure the voltage at the GSC400 terminals.
Figure 6 – Advanced Settings Window
11 of 18