Using the Remote
(2) Numeric Adjustment.
An example of this type of setting is the LCD Contrast parameter in the Operator Setup > Display menu.
Press up and dow n to change the setting. Press enter to select the change. A checkmark w ill be displayed. Pressing enter
w ill checkmark displayed w ill stored value and exit the menu.
(3) Multiple Numeric Adjustments.
An example of this type of setting is the time parameters in the Operator Setup > Date/Time > Time Change menu.
Press up and dow n to scroll to the desired parameter you w ish to change and press enter. The parameter value w ill be
selected. Press up and dow n to change the parameter. When finished press enter. The w hole parameter w ill be selected.
As before press up or dow n to scroll to the next parameter or back to exit the menu.
3.4

Starting and Stopping

The remote panel cannot start the generator if the local controller is in the OFF mode. This is a safety feature. When the
local controller is in the OFF mode the remote controller w ill display "System Off, Start Disabled".
Starting w ith the remote panel can only be accomplished w hen the local controller is in the AUTO mode; you must go to the
local controller and put it in AUTO if the local controller is in the OFF mode. When in AUTO mode the remote w ill display
"System Ready, Waiting to Start". Pressing the Run button on the remote panel w ill start the controller.
When in RUN mode pressing the Off button on the remote w ill shutdow n the controller. If the local controller w as started via
its front panel Run button then you must hold dow n the Off button on the remote panel for at least 3s -- this is referred to as
the forced off feature. It is to discourage remote users from overriding users that started the controller locally.
For installations w ith cooldow n delay, the remote panel cannot be used to cancel cooldow n and reenter the RUN mode.
TOUGH Series Manual
© 2019 DynaGen Technologies Inc
10