DynaGen AST2225 설치 및 사용자 설명서 - 페이지 10
{카테고리_이름} DynaGen AST2225에 대한 설치 및 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. DynaGen AST2225 19 페이지. Automatic transfer switch
Replacement is the reverse of the above procedure. Note that the crank arm must be
positioned flush with the end of the motor shaft and the set screw opposite the flat on the
shaft
3:4 MECHANICAL LIMIT SWITCH ADJUSTMENT
The limit switches controlling the normal and emergency positions of the main
switches, have been factory set to a clearance of 0.020" between the face of the
switch and the limit switch cam, to ensure continued reliable operation. Should it
become necessary to adjust this gap, in the event of replacing a limit switch for
example, the following procedure is recommended (see diagram page 12):
a) Electrically isolate the transfer switch from all power sources. Loosen the
pivot screw and clamp screw to enable the limit switch to rotate about the
pivot screw.
b) Open the cover on the operating arm and remove the pin slider to allow the
limit switch cam to be rotated manually.
c) Insert a 0.020" feeler gauge between the face of the limit switch cam and
the operating plunger of the switch. Rotate the limit switch about the pivot
screw to establish the 0.020" clearance. Tighten the clamp screw and pivot
screw.
d) Rotate the limit switch cam by hand to check the switch operation and
readjust if necessary
e) Replace the pin slider and close the cover.
Manual for AST2225 Series
Automatic
Transfer Switch
10