GAI-Tronics GC-DC1 매뉴얼 - 페이지 3
{카테고리_이름} GAI-Tronics GC-DC1에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. GAI-Tronics GC-DC1 18 페이지. Ez page industrial intercoms
EZ P
I
I
AGE
NDUSTRIAL
NTERCOMS
Internal Settings
The following procedure describes how to change the internal settings. If the intercom will be used as a
Listen/Talk unit or as a Master unit in a balanced line system, then no changes to the internal PCBA's
jumper or switch settings are required.
WARNING
Disconnect power to unit before opening to avoid possible damage to equipment or personal injury.
1. Disconnect power to the unit.
2. Loosen and remove the six screws securing the front cover.
3. Lift out the front panel assembly and tilt to the left. Use caution to ensure that no unnecessary strain
is placed on the attached wiring harnesses.
4. If configuring the unit as a slave, slide the PCBA's mode switch (SW3) to the S
Figure 2.
5. If operating in an unbalanced cable system, reposition the PCBA's jumper P5/J5 from the B
position to the U
NBAL
6. Reinsert the front panel assembly into the rear housing. Ensure that no wires are between the front
panel's gasket and the housing's sealing surface that could be pinched.
7. Reinsert the six screws into the front cover and tighten securely.
8. Reapply the unit power and check for proper operation.
f:\standard ioms - current release\42004 instr. manuals\42004-307g.doc
03/15
position. See Figure 2.
Figure 2. PCBA Outline Detail
Pub. 42004-307G
Page 3 of 16
position. See
LAVE
AL