Automation Direct T1K-08ND3 빠른 시작 매뉴얼 - 페이지 2
{카테고리_이름} Automation Direct T1K-08ND3에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Automation Direct T1K-08ND3 2 페이지. Dc input modules
Terminator I/O Dimensions and Installation
D
IMENSIONS AND
It is important to understand the instal-
lation requirements for your Terminator
I/O system. This will help ensure that the
Terminator I/O products work within
their environmental and electrical limits.
Plan for safety
This catalog should never be used as a
replacement for the technical data sheet
that comes with the products or the
T1K-INST-M Installation and I/O
Manual (It is also available online at
www.automation-direct.com.) The tech-
nical data sheet contains information
that must be followed. The system instal-
lation should comply with all appro-
priate electrical codes and standards.
Unit dimensions and
mounting orientation
Use the following diagrams to make sure
the Terminator I/O system can be
installed in your application. Terminator
I/O units can be mounted horizontally
or vertically. However, to insure proper
airflow for cooling purposes, units
should not be mounted upside-down. It
is important to check the Terminator I/O
dimensions against the conditions
required for your application. For
example, it is recommended to leave 2"
depth for ease of access and cable clear-
ance. However, your distance may be
greater or less. Also, check the installa-
tion guidelines for the recommended
cabinet clearances.
48mm
(1.89in)
80mm
(3.15in)
Power Supply
642
Universal Field I/O
I
NSTALLATION
Ambient Operating Temperature
Storage Temperature
Ambient Humidity
Atmosphere
Vibration Resistance
Shock Resistance
Voltage Withstand (Dielectric)
Insulation Resistance
Noise Immunity
Agency Approvals
48mm
(1.89in)
80mm
(3.15in)
Network Interface Module
Half-size I/O Module
with Base
Terminator I/O Environmental Specifications
32°F to 131°F (0°C to 55°C)
-4°F to 158°F (-20°C to 70°C)
5% to 95% (Non-condensing)
No corrosive gases. The level of environmental
pollution = 2 (UL 840)
MIL STD 810C, Method 514.2
MIL STD 810C, Method 516.2
1500VAC, 1 minute
500VDC, 10M ohm
NEMA ICS3-304
Impulse noise 1us, 1000V
FCC class A
RFI (144MHz, 430MHz 10W, 10cm)
UL, CE, FCC class A, NEC Class 1 Division 2
48mm
(1.89in)
80mm
(3.15in)
Full-size I/O Module
with Base
the Enclosures section
of this desk reference for an
enclosure that may be suitable
for your application
89mm
(3.5in)
80mm
(3.15in)
See
83.3mm
(3.28in)
System Height