Step 4 - Select Power Scheme
Select the appropriate power scheme to meet overall current draw. Using the analysis from the previous sections equates to the
following power scheme possibilities.
Power Scheme Details
1
©2009 - 2012 HID Global Corporation. All rights reserved.
Hi-O CANbus power derived from an external +12VDC or +24VDC power supply. The Hi-O Networked
Controller power is derived from PoE.
Hi-O CANbus connections to the Hi-O Networked Controller shall omit the CANbus V+ and
CANbus GND output connections.
Insert a voltage converter module between the CANBus and Hi-O iCLASS reader.
Insert a UL294 Listed PoE Injector in the Ethernet line to power the Hi-O Networked Controller.
Unprotected
ted
Area
Hi-O iCLASS
SS
Hi-O N
Hi-O Networked
Reader
Voltage Module
EDGE EVO Hi-O Networked Controller
Protected Area
Con
Controller
Ethernet Power
Ethernet Data
12 - 24VDC
Power Supply
CANbus Data
Module
Door Position
Switch
Magnetic Lock
Magne
Local Sounder
Exit Alarm
REX Switch
Remote Area
UL294 PoE
Injector
Ethernet Switch
Door
Physical Access
Control Server
(real-time functions
not required )
INSTALLATION GUIDE
EH400