Automation Direct DURApulse GS21-10P2 빠른 시작 매뉴얼 - 페이지 5

{카테고리_이름} Automation Direct DURApulse GS21-10P2에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Automation Direct DURApulse GS21-10P2 9 페이지. Ac drive

Automation Direct DURApulse GS21-10P2 빠른 시작 매뉴얼
DURApulse GS20 AC Drive Quick-Start Guide
Entering and Exiting "GS2" Mode
GS20 drives that have an equivalent GS2 model (same power and HP rating) have the option of being operated
in "GS2 Mode". This allows you to use the new drive in exactly the same role as an older GS2 drive that needs
to be replaced, or in conjuction with existing GS2 drives.
Note that all drives will come factory standard with GS20 mode as the default setting.

Enter GS2 Mode

Note: To enter GS2 mode, parameters cannot be locked or set to read only, and the PLC must be disabled. If
any of these requirements are not met, you will be unable to set 00.02 to 20.
1) Set parameter 00.02=2, to reset to GS2 mode (1st parameter) and press ENTER.
2) Set parameter 00.02=20 to reset to GS2 mode (2nd parameter) and press ENTER.
3) Reboot the drive by cycling power.
4) Configure GS2 parameters per the tables below.

Exit GS2 Mode

1) Set parameter 09.08=20 to reset to GS20 mode (parameters will reset). Press ENTER.
2) Reboot the drive by cycling power.
3) Configure GS20 parameters per the tables above and in the GS20 User Manual.
DURA
GS2 Parameter Settings
pulse
Parameter
Description
Settings
Group
#
115/230V series–200/208/220/230/240
P00 00 Motor nameplate voltage
460V series–380/400/415/440/460/480
575V series–380 to 637
P00 01 Motor nameplate amps
Drive rated amps times 30 to 100%
P00 02 Motor base frequency
50/60/400
P00 03 Motor base RPM
375 to 9999 rpm
P00 04 Motor maximum RPM
Base RPM (parameter 0.03) to 9999 rpm
P01 00 Stop methods
00–Ramp to stop
P01 01 Acceleration Time 1
0.1 to 600.0 seconds
P01 02 Deceleration Time 1
0.1 to 600.0 seconds
00–General Purpose
P02 00 Volts/Hertz Settings
01–High Starting Torque
P02 02 Auto-torque boost
00 to 10
00–Operation determined by keypad
01–Operation determined by external control. Keypad
STOP enabled.
02–Operation determined by external conrol, keypad
P03 00 Source of Operation Command
STOP disabled.
03–Operation determined by RS232C/RS-485 interface,
keypad STOP is enabled.
04–Operation determined by RS-232C/RS-485 interface,
keypad STOP is disabled.
00–DI1=FWD/STOP
DI2=REV/STOP
01–DI1=RUN/STOP
Multi-function Input Terminals
P03 01
DI2=REV/FWD
(DI1 - DI2)
02–DI1=RUN momentary (N.O.)
DI2=REV/FWD
DI3=STOP momentary (N.C.)
00–External fault (N.O.)
P03 02 Multi-function Input (DI3)
01–External fault (N.C.)
02–External reset
03–Multi-speed/PID SP Bit1
P03 03 Multi-function Input (DI4)
04–Multi-speed/PID SP Bit2
05–Multi-speed/PID SP Bit3
P03 04 Multi-function Input (DI5)
06–Reserved
07–Reserved
08–Reserved
P03 05 Multi-function Input (DI6)
09–Reserved
00–AC Drive Running
01–AC Drive Fault
P03 11 Multi-function Output Terminal 1
02–At Speed
03–Zero Speed
04–Above Desired Freq.
P03 12 Multi-function Output Terminal 2
05–Below Desired Freq.
00–Frequency determined by keypad potentiometer
01–Frequency determined by keypad up/down
02–Frequency determined by 0 to +10V input on AI
terminal with jumpers.
03–Frequency determined by 4 to 20 mA input on AI
P04 00 Source of Frequency Command
terminal with jumpers.
04–Frequency determined by 0 to 20 mA input on AI
terminal with jumpers.
05–Frequency determined by RS-232C/RS-485
communication interface.
00–No Offset
P04 01 Analog Input Offset Polarity
01–Positive Offset
02–Negative Offset
P04 02 Analog Input Offset
0.0 to 100.0 %
P04 03 Analog Input Gain
0.0 to 300.0 %
00–Frequency Hz
P04 11 Analog Output Signal
01–Current A
02–PV
P04 12 Analog Output Gain
00 to 200%
GS20_QSP_1ed 06/29/2020
Parameter
Description
Group
#
P06 31 Present Fault Record
P06 32 Second Most Recent Fault Record
P06 33 Third Most Recent Fault Record
P06 34 Fourth Most Recent Fault Record
P06 35 Fifth Most Recent Fault Record
P06 36 Sixth Most Recent Fault Record
P07 00 Input Terminal for PID Feedback
User
P07 02 PID Setpoint Source
P07 20 Proportional Control
P07 21 Integral Control
P07 22 Derivative Control
P08 00 User Defined Display Function
01–Coast to stop
P08 01 Frequency Scale Factor
P09 08 Restore to Default
02–Fans and Pumps
03–Custom
10–Ext. Base Block (N.O.)
11–Ext. Base Block (N.C.)
12–2nd Accel/Decel Time
13–Speed Hold
14–Increase Speed
15–Decrease Speed
16–Reset Speed to Zero
17–PID Disable (N.O.)
18–PID Disable (N.C.)
99–Input Disable
06–At Maximum Speed
07–Over Torque Detected
08–Above Desired Current
09–Below Desired Current
10–PID Deviation Alarm
DURA
GS2 Parameter Settings
pulse
Settings
User
00–No Fault occured
13–Over-current during
01–Over-current (oc)
decel (OCd)
02–Over-voltage (ov)
14–Over-current during
03–Overheat (oH)
steady state (OCn)
04–Overload (oL)
15–Ground fault or fuse
05–Overload 1 (oL1)
failure (GFF)
06–Overload 2 (oL2)
16–Reserved
07–External Fault (EF)
17–Input Power 3-phase
08–CPU failure 1 (CF1)
loss
09–CPU failure 2 (CF2)
18–External Base-Block
10–CPU failure 3 (CF3)
(bb)
11–Hardware Protection
19–Auto Adjust accel/
Failure (HPF)
decel failure (cFA)
12–Over-current during accel
20–Software protection
(OCA)
code (codE)
00–Inhibit PID operation
01–Forward Acting (Heating Loop) PID feedback, PV from
AVI (0 to +10V)
02–Forward Acting PID feedback, PV from ACI (4 to 20
mA)
03–Reverse Acting (Cooling Loop) PID feedback, PV from
AVI (0 to +10V)
04–Reverse Acting PID feedback, PV from ACI (4 to 20 mA)
00–Keypad
01–Serial Communication
0.0 to 10.0
0.00 to 100.0 seconds (0.00=disable)
0.00 to 1.00 seconds
00–Output Frequency (Hz)
05–Output Voltage (V)
01–Motor Speed (rpm)
06–DC Bus Voltage (V)
02–Output Freq. X P8.01
07–PID Setpoint
03–Output Current (A)
08–PID Feedback (PV)
04–Motor Output Current (%)
09–Frequency Setpoint
0.01 to 160.0
20–Reset to GS20 mode
99–Restore ALL parameters to factory defaults

Cooling and Heat Dissipation

Airflow Rate for Cooling
Model
Flow Rate
Flow Rate
Loss External
Number
(cfm)
(m
3
/hr)
(Heat sink)
GS21-10P2
0.0
0.0
14.2
GS21-10P5
16.0
27.2
29.1
GS21-11P0
GS21-20P2
0.0
0.0
16.3
GS21-20P5
29.1
GS21-21P0
29.1
GS21-22P0
16.0
27.2
70.0
GS21-23P0
244.5
GS23-2010
53.7
91.2
374.2
GS23-2015
67.9
115.2
492.0
GS23-2020
GS23-20P2
0.0
0.0
16.5
GS23-20P5
31.0
GS23-21P0
10.0
16.99
50.1
GS23-22P0
76.0
GS23-23P0
16.0
27.2
108.2
GS23-25P0
192.8
GS23-27P5
23.4
39.7
164.7
GS23-4010
234.5
GS23-4015
53.7
91.2
319.8
GS23-4020
423.5
GS23-4025
67.9
115.2
501.1
GS23-4030
17.6
GS23-40P5
10.0
16.99
30.5
GS23-41P0
45.9
GS23-42P0
60.6
GS23-43P0
16.0
27.2
93.1
GS23-45P0
132.8
GS23-47P5
23.4
39.7
108.4
GS23-5010
0.0
0.0
23.5
GS23-51P0
10.0
16.99
38.1
GS23-52P0
56.6
GS23-53P0
16.0
27.2
76.1
GS23-55P0
23.4
39.7
93.9
GS23-57P5
• External Flow Rate is across the heat sink.
• When calculating power dissipation (Watt
• Internal Flow Rate is through the chassis.
Loss), use the Total value. Heat dissipation
• Published flow rates are the result of active
shown in the chart is for installing a single
cooling using fans, factory installed in the
GS20 drive in a confined space.
drive.
• When installing multiple drives, the volume
• Unpublished flow rates ( - ) are the result
of heat/power dissipation should be the
of passive cooling in drives without factory
heat/power dissipated by a single GS20 drive
installed fans.
multiplied by the number of GS20 drives.
• The required airflow shown in the chart
• Heat dissipation for each model is calculated
is for installing a single GS20 drive in a
by rated voltage, current and default carrier
confined space.
frequency.
• When installing multiple GS20 drives,
the required air volume would be the
required air volume for a single GS20 drive
multiplied by the number of GS20 drives.
DURApulse GS20 AC Drive Quick-Start Guide – 1st Ed 06/29/2020
Power Dissipation (Watts)
Internal
Total
8.0
10.0
18.0
13.1
27.3
23.9
53.0
8.0
10.3
18.3
14.5
30.8
20.1
49.2
23.9
53.0
35
105
79.6
324.1
86.2
460.4
198.2
690.2
8.6
10.0
18.6
12.6
29.1
13.2
44.2
24.2
74.3
30.7
106.7
40.1
148.3
53.3
246.1
55.8
220.5
69.8
304.3
74.3
394.1
181.6
605.1
200.3
701.4
11.1
28.7
17.8
48.3
21.7
67.6
22.8
83.4
42
135.1
39.5
172.3
51
159.4
12.5
36
19
57.1
22.2
68.8
30
106.1
37
130.9
Page 5