mounting

.........................................................................................................................
.........................................................................................................................
Select A Suitable Location
This device is designed for indoor use only. If
installing in an external location, the DMC810GL
must be housed in a suitable well-ventilated
enclosure.
Choose a dry location that will be
accessible after the installation is complete. To
ensure the cooling system functions correctly, the
DMC810GL should only be mounted vertically, the
right way up. The DMC810GL will generate heat
when operating, approximately 2 Watts per Amp
of load connected to the dimmed channels only,
and requires an air gap of 200mm on each side
and at the top and bottom of the device. This air
gap is also required to ensure serviceability of the
DMC810GL without complete removal from the
mounting surface. This device may emit some
mechanical noise. Take this into account when
deciding the mounting location.
Fixing the Device
The DMC810GL has integral mounting brackets
attached to the enclosure.
designed to accommodate 4 fixing screws up to
8mm diameter. The DMC810GL can be fixed to
the wall without opening the cabinet or removing
covers. Make sure no dust or other debris enters
the device during installation. Do not leave the
front cover off for any length of time. Excessive
dust and dirt can degrade the cooling of internal
components.
Allow For Cable Entry
Supply and load cables enter the enclosure at the
top.
If these cables are fed from below the
mounting position, they should be routed around
the enclosure to enter at the top. An alternative
method is to stand the enclosure off from the
mounting surface by mounting it on a cable tray or
a Unistrut style product. The cables can then be
routed between the enclosure and the mounting
surface, and enter the enclosure via the cutout
provided on the mounting face.
cables enter at the bottom of the enclosure.
Control cables should never be run in the mains
voltage sections of the enclosure.
DMC810GL Instruction Manual Rev B.DOC
The brackets are
The control
4