Specifications

Environmental
Specifications
Operating Temperature
Storage Temperature
Operating Humidity
Air Composition
Vibration
Shock
Voltage Isolation
Insulation Resistance
Noise
Operating
Specifications
Power Budget Requirement
Maximum number of modules
Location of module
Interface
Baud Rates
Maximum Distance
Protocol
Diagnostics
Note 1: Also compatible with Hostlink and/or CCM2 protocols. These names were used by previous vendors of
compatible Koyo designed products.
32 F to 140 F (0 to 60 C)
–4 F to 158 F (–20 to 80 C)
5 to 95% (non-condensing)
No corrosive gases permitted
MIL STD 810C 514.2
MIL STD 810C 516.2
1500 VAC, 1 minute duration
10M ohms at 500 VDC
NEMA ICS3–304
500 ma @ 5 VDC
limited only by power budget
CPU base only
any slot except Slot 0 or CPU slot
Serial RS232C / RS422
half-duplex, DTE, Asynchronous,
8 bits/character
300 to 38.4K baud, switch selectable
RS232C – 49ft (15 meters)
RS422 – 3300 feet (1000 meters)
Direct NET
1
K-sequence (proprietary)
MODBUS
RTU
Automatic check of ROM/RAM,
communications, switch settings,
and LEDs
7 7