INSTALLATION INSTRUCTIONS
The device shall be mounted on DIN rail in a vertical and upright orientation.
For optimum operation and long life follow these instructions:
When the devices are installed side by side it is necessary to separate them by
the following minimum distances:
• 10 mm if UL certification is required.
• 5 mm if UL certification is not required.
Make sure that sufficient air flow is provided for the device. Avoid placing
raceways or other objects where they could obstruct the ventilation slits.
Avoid mounting the devices above appliances generating heat; ideally locate
them in the lower part of the panel.
Install the device in a place without vibrations.
Avoid routing conductors near power signal cables (motors, induction ovens,
inverters, etc.). Use shielded cable for connecting signals; ground shield at one
end only.
DEFAULT CONFIGURATION
• IP Address: 192.168.1.100
• Modbus Address: 1
• Default user name: admin
• Default password: password
MODBUS REGISTERS
Register
Description
40002
Firmware [0]
40003
Firmware [1]
40004
-Reserved-
40005
-Reserved-
40007
Node ID
40011
System Flags
40013
Watchdog timer
40031
Input Type, Channel 0
40032
Input Type, Channel 1
40033
Input Type, Channel 2
40034
Input Type, Channel 3
40041
Analog Input (0) - Ch0
40042
Analog Input (1) - Ch1
40043
Analog Input (2) - Ch2
40044
Analog Input (3) - Ch3
40050
Break Status
41241
Offset Channel 0
41242
Offset Channel 1
41243
Offset Channel 2
41244
Offset Channel 3
FRONT PANEL LEDS
LED
COLOR
PWR
GREEN
STS
YELLOW
MECHANICAL DIMENSIONS
MM [IN]
POWER
GREEN LED
STATUS
YELLOW LED
100.0
3.94
RESET BUTTON
22.5
0.89
AutomationDirect.com reserves the right to modify the characteristics of its products totally or in part without warning at any time.
PINOUT
Access
Pin
Description
1
IN0
RO
RO
2
REF0
RO
3
GEN0
4
N.C.
RO
R/W
5
IN1
R/W
6
REF1
R/W
7
GEN1
R/W
8
N.C.
R/W
9
IN2
R/W
10
REF2
R/W
11
GEN2
RO
12
N.C.
RO
13
IN3
14
REF3
RO
RO
15
GEN3
RO
16
N.C.
R/W
R/W
R/W
R/W
STATE
DESCRIPTION
ON
Device powered
OFF
Device not powered
BLINK
Watchdog alarm
OFF
Device in RUN mode
BLINK
Device in INIT mode
120.0
4.72
POWER SUPPLY (1)
+VS
O
P
-VS
NOTE: (1) To maintain the UL listing use a Class 2 or SELV and
limited energy power supply.
(2)
See User Guide for instructions on using the INIT feature.
ANALOG INPUTS
RTD/RES 2 WIRES
INPUT 0
3
Channel
1
IN 0
2
RTD/RES 3 WIRES
IN 1
INPUT 0
3
IN 2
1
2
IN 3
POTENTIOMETER
INPUT 0
3
1
2
NOTES:
All input channels are isolated.
ISOLATED ELECTRICAL SUBSYSTEMS
CH 0
CH 1
3-WIRE
CONNECTOR
CH 2
CH 3
Each block represents a subsystem which is isolated
49.3
from each other subsystem.
1.94
50.7
WEEE compliance -
2.00
These devices comply with the WEEE directive.
Dispose of properly.
16-WIRE
CONNECTOR
INIT FUNCTION (2)
INIT
Q
+
14–30 VDC
-
P
-VS
INPUT 1
INPUT 2
7
11
5
9
6
10
INPUT 1
INPUT 2
7
11
5
9
6
10
INPUT 1
INPUT 2
7
11
5
9
6
10
ON: Short INIT
to -VS
INPUT 3
15
13
14
INPUT 3
15
13
14
INPUT 3
15
13
14
ETH.
POWER
SUPPLY
1st Edition, 01/2020