System Configuration
On the System Configuration page, set the basic system parameters.
• Name: set a helpful name to identify this device; max 15 alphanumeric characters.
• Modbus Address: set the Modbus address of this device; the default value is 1. In INIT mode this value is temporarily set to 245.
• Watchdog Enable (ref. "System Flags" register): enables the Watchdog event (0 = Watchdog disabled, 1 = Watchdog enabled).
• Timeout (ref. "Watchdog timer" register): set the value in seconds of the Watchdog timer.
• Watchdog Event (ref. "System Flags" register): this flag signals that the Watchdog condition has occurred
(0 = Normal condition; 1 = Alarm condition).
• Power-up Event (ref. "System Flags" register): this flag is forced to 1 at each power-on and indicates that the device has been
switched off or a power cycle has occurred. (0 = power cycle has not occurred ; 1 = power cycle has occurred ).
Click Save to apply and store the modified parameters. To read the parameters from the device click Refresh.
SIO-MB04RTDS User Guide, 1st Edition
Stride Field I/O