Dynamic DYN-120 설치 및 운영 매뉴얼

{카테고리_이름} Dynamic DYN-120에 대한 설치 및 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Dynamic DYN-120 4 페이지. 2” and 2” tandem polarized-media air cleaners

2" and 2" Tandem
Polarized-Media

Air Cleaners

Installation
&
Operation
Manual
All Dynamic Air Cleaners operate with the same basic principles of active-field polarized media. In the 2" Panel
Air Cleaner, the 24 VAC input to the Powerhead is stepped up to 7 kV (DC) at very low current. This voltage is
applied to the center screen inside the replaceable media pad. This creates an electrostatic field between the
center screen and the grounded exterior metal screens. The electrostatic field polarizes both the fibers in the
media and airborne contaminants. These are then attracted to and collected by the media fibers. When the
pads are loaded, they are easily removed and replaced.
Dynamic 2" Air Cleaners typically slide into the standard 2" racks in the air handler. They are available as
individual Panels or as Tandem Panels. Typically, a Panel Air Cleaner is used when there is only one filter per
row. Each Panel is wired separately. Tandem Panels are used when there are multiple Air Cleaners per row.
They are connected mechanically and electrically to the adjacent Air Cleaner, and there is one electrical
connection per row. The entire row may be pulled out for service. Neoprene foam strips are used on the mating
faces of the Air Cleaners in a row to block the flow of air between Panels.
Section I. Sizing
While Air Cleaner height is consistent with filter rack height, Air Cleaner widths are typically sized to minimize the
number of Air Cleaners in a row and fill the width of the rack in the unit. Keeping the Air Cleaner width consistent
will also standardize replacement media pad size. For example, a rack that has three 24"x24"x2" passive filters
would typically take two 36"x24"x2" Dynamic Tandem Panels. Make sure that there is enough room to slide out
the larger Panel. In the above example, the Powerhead would go on top on the long side. When ordering, the
first dimension is the side with the Powerhead. Therefore, a 36"x24" Tandem is not the same as a 24"x36"
Tandem. Assuming a set of two, the first would give you an assembly that is 72" wide and 24" high and the
second would yield an assembly that is 48" wide and 36" high.
Like passive filters, 2" Panels are undersized from the nominal dimensions. They are undersized ½" on height
(the height of the filter track) and ¼" on width. Whenever possible, and on all retrofit applications, measure the
filter racks rather than relying on the nominal dimensions of the passive filters.
Section II. Installation
Dynamic 2" Panels slide into the existing filter racks. The required 24 VAC may come from an on-board source,
a dedicated transformer, or a Dynamic Control Panel, with optional pressure transmitter gauge. Make certain
that there is sufficient capacity (3 VA) when using an on-board transformer. Follow all applicable local codes.
Make certain the air handler is off when installing the Panels.
In the case of a Panel Air Cleaner, each Panel will require an electrical connection. With Tandem Panels, each
row requires its own input.
1