2. Functionality
: accurately measures phase voltages, line voltages, line currents,
1. Multi-function
active, reactive and apparent power, phase and total power factors, frequency and
maximum demand.
2. Harmonics
: the IC995 measures component harmonics up to the 31st inst and THD
for both current and voltage.
3. Network analysis
: displays 4-quadrant energies, including active capacitive energy,
active inductive energy, reactive capacitive energy and reactive inductive energy. Also
measures current "K" factor, voltage crest factor, waveform factor and degree of voltage
and current imbalance.
: the IC995 is provided with 4 digital inputs, 2 digital relay outputs,
4. Inputs/Outputs
1 volt-free pulse output (set at 10kWh/pulse) and 1 RS485 (Modbus protocol) output
in order to satisfy remote meter reading and system control monitoring.
3. Technical features
FEATURE
VALUES
Network
1PH2W, 3P3W, 3P4W
Frequency
45~65Hz
Voltage
Normal: AC 100V, 400V
INPUT
Overloading: 600V (continuous); 1000V / 30s
Consumption: < 0.2VA
Current
Normal: AC 1A, 5A
Overloading: 6A(continuous); 50A /1s
Consumption: < 0.2VA
Pulse output
Mode: Optocoupler pulse output, volt free
Communication
RS485 (Modbus-RTU)
Digital input (DI)
4 drying contact inputs, with +5V power
Digital output (DO)
Mode: 2 NO contacts (AC 250V/3A, DC 30V/3A)
Accuracy
Frequency 0.01Hz, reactive energy 1 class, others 0.5 class
Display
LCD with backlight
Power supply
AC/DC 85~270V; consumation: ≤4VA
Isolation
Power / current input / voltage input: AC2kV/1min;
Power / Digital inputs / RS485: AC1.5kV/1min;
Inputs / outputs / housing >5M_
Environment
Working T: -10C~+45C; Storing T: -20C~+70C
Relative humidity: 5%~95% Non-Condensing; Altitude: ≤2500m
Material used
Polycarbonate v.0 rated
The IC 995 meter is manufactured in compliance to:
EN 62052-11: 2004
(AC) General requirements
2
EN 62053-21: 2003
(Particular requirements part 21 static meters)
8
EN61010:2001
LVD approval
Dimensions
96
Connection Diagram 3 phase 4 wire, 230/400v 50Hz
230 volt
Kwh
Auxiliary
Pulse
Supply
Output
The meter must
have Auxiliary Power
Supply connected
Direc tion of Current
M
L3
A
L2
I
N
L1
S
Neutral
* it is important P2 faces the Load side
70
90
85
RS 485
Tx+
Tx-
Shield
Terminals 34-36
Digital Inputs
Terminals 24-28
Digital Outputs
S2
S1
P1
S1 S2
L
P1
O
S1 S2
A
P1
D
3